Rated voltage
230 V~
Rated frequency
50 Hz
Rated current
6 A
Protection class
I
Protection
IP X 4 D to
EN 60529
Permissible ambient temperature
&
during operation
0 to +40 °C
&
during storage
and transport
-20 to +65 °C
Electronic tempera-
ture limiter setting
82 °C
Temperature limiter
setting
100 °C (fixed)
Line fuse (mains)
max. 16 A
–
Power consumption
&
Circulation pump
max. 115 W
&
Burner
max. 60 W
&
Control unit
max. 10 VA
Gas boiler, category: II
2ELL3P
Rated output range T
V
/T
R
50/30 °C
kW
6.6 to 26
Rated thermal load range
kW
6.3 to 24.7
Connection values
*
1
In relation to the max. load
with
Natural gas E
m
3
/h
2.65
Natural gas LL
m
3
/h
3.08
LPG
m
3
/h
1.94
Product ID
CE
–
0085 BO 0338
Product characteristics (to EnEV [Germany])
Rated output range
kW
6.6 to 26
Efficiency
µ at
&
100 % of rated output
%
96.3
&
30 % of rated output
%
107.4
Standby loss
q
B,70
*
2
%
0.7
Power consumption
*
2
at
&
100 % of rated output
W
207
&
30 % of rated output
W
69
Specification
119
Specification
5692
731
GB
*1
The supply values are only for documentation purposes (e.g. in the gas contract applica-
tion) or to estimate the supplementary volumetric settings. Because of factory settings,
the gas pressure must not be altered from these settings. Reference: 15 °C, 1013 mbar.
*2
Max. limit to EnEV [Germany]
Содержание VITODENS 333-F WS3A
Страница 109: ...A1 Main PCB A2 Power supply unit Connection and wiring diagram external connections 109 Designs 5692 731 GB ...
Страница 113: ...Parts lists cont 113 Parts lists 5692 731 GB ...
Страница 114: ...Parts lists cont 114 Parts lists 5692 731 GB ...
Страница 115: ...Parts lists cont 115 Parts lists 5692 731 GB ...
Страница 116: ...Parts lists cont 116 Parts lists 5692 731 GB ...
Страница 117: ...Parts lists cont 117 Parts lists 5692 731 GB ...