Boiler control unit
Vitotronic 200-H
Vitotronic 200-H
Vitocom
Control unit trans-
mits outside tem-
perature
Set
code "97:2"
Control unit re-
ceives outside tem-
perature
Set
code "97:1"
Control unit re-
ceives outside tem-
perature
Set
code "97:1"
—
LON subscriber fault
monitoring
Code "9C:20"
LON subscriber
fault monitoring
Code "9C:20"
LON subscriber
fault monitoring
Code "9C:20"
—
Updating the LON subscriber list
Only possible if all subscribers are
connected and the control unit is pro-
grammed to be fault manager (code
"79:1").
Press the following keys:
1.
L
+
d
simultaneously for
approx. 2 s.
Subscriber check
initiated (see page 37).
2.
e
The subscriber list is
updated after approx.
2 min.
The subscriber check is
completed.
Carrying out a subscriber check
Communication with the system devices connected to the fault manager is
tested with a subscriber check.
Precondition:
&
The control unit must be pro-
grammed as
fault manager
(code
"79:1")
&
The LON subscriber number must
be programmed in all control units
(see page 36)
&
The LON subscriber list in the fault
manager must be up to date (see
page 36)
A
Consecutive number in the sub-
scriber list
B
Subscriber number
Further details regarding the individual steps
(cont.)
37
Commissioning, inspection, maintenance
5692
731
GB
Содержание VITODENS 333-F WS3A
Страница 109: ...A1 Main PCB A2 Power supply unit Connection and wiring diagram external connections 109 Designs 5692 731 GB ...
Страница 113: ...Parts lists cont 113 Parts lists 5692 731 GB ...
Страница 114: ...Parts lists cont 114 Parts lists 5692 731 GB ...
Страница 115: ...Parts lists cont 115 Parts lists 5692 731 GB ...
Страница 116: ...Parts lists cont 116 Parts lists 5692 731 GB ...
Страница 117: ...Parts lists cont 117 Parts lists 5692 731 GB ...