Coding in the delivered condition
Possible change
9C:20
Monitoring LON sub-
scribers.
If a subscriber fails to
respond, the values de-
faulted inside the con-
trol unit will be used
after 20 min. Only then
will a fault message be
issued (only for weath-
er-compensated control
units)
9C:0
No monitoring
9C:5
to
9C:60
The time is adjustable
from 5 to 60 min
9F:8
Differential temperature
8 K; only in conjunction
with the mixer circuit
(only for weather-com-
pensated control units)
9F:0
to
9F:40
Differential temperature
adjustable from 0 to 40 K
Heating circuit A1/M2
A0:0
Without remote control
(only for weather-com-
pensated control units)
A0:1
With Vitotrol 200 (auto-
matic recognition)
A0:2
With Vitotrol 300 (auto-
matic recognition)
Code 2
(cont.)
52
Coding
5692
731
GB