Coding in the delivered condition
Possible change
A3:2
Outside temperature
below 1 °C: Heating cir-
cuit pump "ON"
Outside temperature
above 3 °C: Heating cir-
cuit pump "OFF"
!
Please note
When selecting a
value below
1 °C, there is a
risk of pipes out-
side the thermal
envelope of the
building being
damaged by
frost.
The standby
mode, in particu-
lar, should be
taken into con-
sideration, e.g.
during holidays.
A3:-9
to
A3:15
Heating circuit pump
"ON/OFF" (see the fol-
lowing table)
Parameter
Heating circuit pump
Address A3:...
"ON"
"OFF"
-9
-10 °C
-8 °C
-8
-9 °C
-7 °C
-7
-8 °C
-6 °C
-6
-7 °C
-5 °C
-5
-6 °C
-4 °C
-4
-5 °C
-3 °C
-3
-4 °C
-2 °C
-2
-3 °C
-1 °C
-1
-2 °C
0 °C
0
-1 °C
1 °C
1
0 °C
2 °C
2
to
1 °C
to
3 °C
15
14 °C
16 °C
Code 2
(cont.)
53
Coding
5692
731
GB