70
!
Please note
Refrigerant can escape when working on the
refrigerant circuit.
Work on the refrigerant circuit must
only
be car-
ried out by a certified contractor (in accordance
with EC 842/2006 and 303/2008).
Check the floor area, valves and all visible solder joints
for traces of oil.
Note
Traces of oil indicate a leak in the refrigerant circuit.
Have your heat pump checked over by a refrigeration
engineer.
Filling and venting on the secondary side
Unsuitable fill and top-up water increases the level of
deposits and corrosion. This can lead to system dam-
age.
Observe VDI 2035 regarding quality and amount of
heating water, including fill and top-up water.
■
Flush the heating system thoroughly before filling.
■
Only fill with water of potable quality.
■
If the fill and top-up water has a water hardness
greater than 16.8 °dH (3.0 mol/m
3
), it must be soft-
ened, e.g. using the small softening system for heat-
ing water: See the Vitoset pricelist.
!
Please note
Escaping liquids can lead to electrical defects.
Protect electrical components of the heat pump
from escaping liquids.
Note
Before
filling the system, observe VDI 2035 part 1.
Fig. 66
A
Drain valve
B
Manual air vent valve
1.
Open any non-return valves installed on site.
2.
Check the pre-charge pressure of the expansion
vessel (see page 71).
3.
Fill the secondary circuit via the on-site BDF valve
(flush) and vent the circuit.
Commissioning, inspection, maintenance
Checking the refrigerant circuit for leaks
(cont.)
5692878
Содержание Vitocal 350-A AWHI 351.A14
Страница 22: ...22 Fig 13 Installation sequence Type AWHI 351 A only Fitting the supplied floor mat 5692878 Installation ...
Страница 26: ...26 3x 8 9 3x 3x 3x Fig 17 Installation sequence Fitting the outer panels cont 5692878 Installation ...
Страница 27: ...27 10 3x 3x 2x 11 Fig 18 Installation sequence Fitting the outer panels cont 5692878 Installation ...
Страница 30: ...30 Type AWHI 351 A 1 Fig 22 Installation sequence Siting the heat pump cont 5692878 Installation ...
Страница 66: ...66 Fitting the front panel 1 2 Fig 64 Installation sequence Closing the heat pump cont 5692878 Installation ...
Страница 82: ...82 Troubleshooting Repairs cont 5692878 Maintenance ...
Страница 101: ...101 Parts list type AWHI 351 A Heat pump module cont 5692878 Components ...
Страница 104: ...104 Parts list type AWHI 351 A Base frame cont 5692878 Components ...
Страница 110: ...110 Silencer hood 0001 0002 0001 Fig 86 Parts list type AWHO 351 A Casing cont 5692878 Components ...
Страница 114: ...114 0007 0007 0003 0005 0003 0002 0001 0006 0005 0008 Fig 88 Parts list type AWHO 351 A Air module 5692878 Components ...
Страница 125: ...125 Parts list type AWHO 351 A Heat pump module cont 5692878 Components ...