54
Terminals
Function
Explanation
X3.8
X3.9
Contact humidistat
or
Jumper
Requires floating contact:
■
Closed: Safety chain has continuity.
■
Open: Safety chain interrupted; heat pump shut
down.
■
Breaking capacity 230 V~, 0.15 A
Connect on site:
■
Connected in series, if both safety components
are installed.
■
Insert jumper if no safety components are
installed.
X3.10
X3.11
Fault message, lag heat pump in a cas-
cade
or
Jumper
Requires floating contact:
■
Closed: No faults
■
Open: Fault
■
Breaking capacity 230 V~, 0.15 A
No jumper should be installed if a message con-
tact is connected.
X3.12
X3.13
or at external
H1 extension
"External demand" signal (external starting
of compressor and pumps, mixer in control
mode or OPEN, changeover of operating
status for several system components)
Requires floating
N/O
contact:
■
Closed: Demand
■
Open: No demand
■
Breaking capacity 230 V, 2 mA
Note
■
These or other external functions, such as
swimming pool heating, cascade or external set
value default can alternatively be connected via
external H1 extension.
"External H1 extension" installation in-
structions
■
If a swimming pool heating facility is connected
to external H1 extension,
no
other external
function can be connected to external H1 exten-
sion.
X3.17
X3.18
MCB/fuse F1 6.3 A (slow)
X5/X7
Control cable 230 V~
Terminals for connecting cable to the control pan-
el
Controller and sensor PCB (sensors)
Set the required parameters during commissioning;
see from page 73.
Note
■
Plug F11:
Nothing
should be connected to plug F11 on site.
■
Flow temperature sensor for heating circuit with
mixer (M3):
The flow temperature sensor for one heating circuit
with mixer (M3) is connected to the mixer extension
kit (accessories).
Plug
Sensors/terminals
Type
(PTC)
F0
Outside temperature sensor
Ni500
F4
(X5.6/X5.7)
Buffer temperature sensor
Pt500
Installation sequence
Heat pump control unit electrical connections
(cont.)
5692878
Installation
Содержание Vitocal 350-A AWHI 351.A14
Страница 22: ...22 Fig 13 Installation sequence Type AWHI 351 A only Fitting the supplied floor mat 5692878 Installation ...
Страница 26: ...26 3x 8 9 3x 3x 3x Fig 17 Installation sequence Fitting the outer panels cont 5692878 Installation ...
Страница 27: ...27 10 3x 3x 2x 11 Fig 18 Installation sequence Fitting the outer panels cont 5692878 Installation ...
Страница 30: ...30 Type AWHI 351 A 1 Fig 22 Installation sequence Siting the heat pump cont 5692878 Installation ...
Страница 66: ...66 Fitting the front panel 1 2 Fig 64 Installation sequence Closing the heat pump cont 5692878 Installation ...
Страница 82: ...82 Troubleshooting Repairs cont 5692878 Maintenance ...
Страница 101: ...101 Parts list type AWHI 351 A Heat pump module cont 5692878 Components ...
Страница 104: ...104 Parts list type AWHI 351 A Base frame cont 5692878 Components ...
Страница 110: ...110 Silencer hood 0001 0002 0001 Fig 86 Parts list type AWHO 351 A Casing cont 5692878 Components ...
Страница 114: ...114 0007 0007 0003 0005 0003 0002 0001 0006 0005 0008 Fig 88 Parts list type AWHO 351 A Air module 5692878 Components ...
Страница 125: ...125 Parts list type AWHO 351 A Heat pump module cont 5692878 Components ...