Vitocal 350-A, type AWHO 351.A20
■
Flow/return lines: 2 x DN 40
■
Adaptors: DN 40 to R 1
¼
■
Lines are fed into building
Q
through a wall duct
with expanding mortar (on site).
■
Provide a drain & fill facility
S
for heating water flow
and return in the building near an external wall and
0.8 m below ground level.
Note
In buildings at ground level, provide a thermally insu-
lated duct or enable draining of the heat pump with
compressed air.
Frost protection
If the heat pump control unit and heating circuit pump
are ready for operation, the frost protection function of
the heat pump control unit is enabled. Drain the sys-
tem via the drain & fill facility
S
when the heat pump
is taken out of use or if the power fails for a long
period.
In heat pump systems where a power failure would not
be detected (holiday home), the heating circuits can be
operated with suitable antifreeze. To ensure trouble-
free heat pump operation, use antifreeze based on gly-
col. Ready-mixed solutions ensure an even distribution
of concentrate.
Recommendation: Use Viessmann "Tyfocor" heat
transfer medium which is based on ethylene glycol
(ready-mixed down to
−
19 °C, light green).
Power cable
M
Observe the technical connection requirements
imposed by your local power supply utility.
■
Run the power cable to control panel
M
outside the
building as an SWA cable (NYY) or route an NYM
cable inside a KG conduit.
■
Cable length required in the heat pump from top
edge of foundation: Min. 2.6 m.
Connecting cables
N
Route prepared connecting cables (control cable
230 V~, LV lead < 42 V)
N
outside the building in a
KG conduit DN 100. Protect the plugs at the ends of
the cables from dirt and damage (e.g. with bubble
wrap).
Cable length required in the heat pump from top edge
of foundation
■
Control cable 230 V~: Min. 0.9 m
■
LV lead < 42 V: Min. 0.7 m
Routing KG conduits
C
,
D
■
Provide a wire pull for the cables (
M
,
N
).
■
To facilitate the routing of cables D through the KG
conduit, avoid 90° bends; instead use 3 x 30° or 2 x
45°.
■
Route the KG conduit with a slope towards the heat
pump and fit a condensate drain if required.
■
Ensure that wall ducts
R
are moisture-proof and
waterproof.
■
Seal the apertures of the KG conduit so that no ani-
mals or moisture can enter the building.
Preparing for installation
External heat pump
(cont.)
5692878
Installation
Содержание Vitocal 350-A AWHI 351.A14
Страница 22: ...22 Fig 13 Installation sequence Type AWHI 351 A only Fitting the supplied floor mat 5692878 Installation ...
Страница 26: ...26 3x 8 9 3x 3x 3x Fig 17 Installation sequence Fitting the outer panels cont 5692878 Installation ...
Страница 27: ...27 10 3x 3x 2x 11 Fig 18 Installation sequence Fitting the outer panels cont 5692878 Installation ...
Страница 30: ...30 Type AWHI 351 A 1 Fig 22 Installation sequence Siting the heat pump cont 5692878 Installation ...
Страница 66: ...66 Fitting the front panel 1 2 Fig 64 Installation sequence Closing the heat pump cont 5692878 Installation ...
Страница 82: ...82 Troubleshooting Repairs cont 5692878 Maintenance ...
Страница 101: ...101 Parts list type AWHI 351 A Heat pump module cont 5692878 Components ...
Страница 104: ...104 Parts list type AWHI 351 A Base frame cont 5692878 Components ...
Страница 110: ...110 Silencer hood 0001 0002 0001 Fig 86 Parts list type AWHO 351 A Casing cont 5692878 Components ...
Страница 114: ...114 0007 0007 0003 0005 0003 0002 0001 0006 0005 0008 Fig 88 Parts list type AWHO 351 A Air module 5692878 Components ...
Страница 125: ...125 Parts list type AWHO 351 A Heat pump module cont 5692878 Components ...