Setting of the maximum temperature
inside the DHW cylinder.
Renewed heating will be prevented
after this temperature has been
reached, until the temperature has
dropped by at least 5 K.
Danger
DHW at temperatures > 60 °C
will lead to scalding.
At these temperatures, install
anti-scalding protection on site.
Access
&
"
System settings
"
&
"
Program
"
&
"
DHW
"
&
"HW buf. storage max."
(
T
/
U
)
Standard setting
60 °C
Setting range
20 to 80 °C
Hysteresis DHW electric heater/hysteresis
These settings determine at what
deviation from the selected set DHW
cylinder temperature of the DHW
cylinder ("
DHW T buffer storage
")
the cylinder heating by the heat pump
("
Hysteresis
") or additionally by the
electric heater ("
Hyst. HW e-heat-
ing
") is to be switched ON or OFF.
DHW cylinder maximum
96
DHW control unit settings
55
92
901
GB