Fault messages
Cause
Measures
D4
Regulated HP 1
Air inside the heating
circuit
Vent the heating circuit
Secondary pump or
heating circuit pump
stalled
Check the secondary pump
or heating circuit pump
Heating circuit con-
taminated
Flush the heating circuit
DA
Room tempera-
ture sensor HC 1
Short circuit
Check the sensor; replace if
required
DB
Room tempera-
ture sensor HC 2
DD
Room tempera-
ture sensor HC 1
Lead broken
Check the terminals; replace
the sensor, if required
GB
Room tempera-
ture sensor HC 2
Reset the high limit safety cut-out
!
Please note
Touching 'live' components in
the working area can result in
the transfer of dangerous body
currents.
Ensure the device is at zero
volts before carrying out any
electrical work and before
resetting the high limit safety
cut-out.
Note
The high limit safety cut-out is located
below the cover shielding the access
to the electrical terminals of the elec-
tric heater (at the bottom r.h. side of
the device).
1.
Remove cover
A
.
2.
Reset the high limit safety cut-out.
For this, push in the red button visi-
ble inside the aperture.
3.
Fit cover
A
.
Control unit diagnostics
(cont.)
63
Troubleshooting
55
92
901
GB
Service
Содержание VITOCAL 300
Страница 19: ...Connection diagram Open CLOSE System version 1 cont 19 Preparing for installation 5592 901 GB...
Страница 22: ...Connection diagram Open CLOSE System version 2 cont 22 Preparing for installation 5592 901 GB...
Страница 66: ...Main menu Information A See page 67 Menu structure overview Information 66 Control unit settings 5592 901 GB...
Страница 137: ...Control PCB 137 Connection and wiring diagrams 5592 901 GB Service...
Страница 140: ...Parts lists cont 140 Parts lists 5592 901 GB...
Страница 141: ...Parts lists cont 141 Parts lists 5592 901 GB Service...
Страница 159: ...159 5592 901 GB...