A
Flow temperature
B
Outside temperature
C
Cooling curve
D
Cooling curve with a higher level
(
C
offset)
E
Cooling curve with a greater slope
Access
&
"
System settings
"
&
"
Program
"
&
"
Heating circuit
"
&
"
Heating circuit 1/2
"
&
"Cooling curve level"
("
+LEV
"/"
−
LEV
")
or
"Slope Cooling curve"
("
+SLOPE
"/"
−
SLOPE
")
Standard setting
Setting range
"
Cooling curve level
"
0
-15 to 40
"
Slope Cooling curve
"
1.2
0.0 to 3.5
Natural cooling (at the heating circuit) with mixer
Select "Yes" for this setting if a mixer
is used for the natural cooling func-
tion.
The primary cooling pump can be
switched by the natural cooling exten-
sion kit as two-point controller, if no
mixer is used. In this case select "No"
for this setting.
Access
&
"
System settings
"
&
"
Program
"
&
"
Heating circuit
"
&
"
Heating circuit 1/2
"
&
"NC with mixer"
("
YES
"/"
NO
")
Standard setting
NO
Setting range
YES/NO
Level/Slope, cooling curve
(cont.)
113
Heating circuit control settings
55
92
901
GB
Service
Содержание VITOCAL 300
Страница 19: ...Connection diagram Open CLOSE System version 1 cont 19 Preparing for installation 5592 901 GB...
Страница 22: ...Connection diagram Open CLOSE System version 2 cont 22 Preparing for installation 5592 901 GB...
Страница 66: ...Main menu Information A See page 67 Menu structure overview Information 66 Control unit settings 5592 901 GB...
Страница 137: ...Control PCB 137 Connection and wiring diagrams 5592 901 GB Service...
Страница 140: ...Parts lists cont 140 Parts lists 5592 901 GB...
Страница 141: ...Parts lists cont 141 Parts lists 5592 901 GB Service...
Страница 159: ...159 5592 901 GB...