1.
Flip up the fuse top.
Note
Opening automatically cuts the
power.
2.
Open the top part from the side
using a screwdriver.
Phase monitor
The phase monitor is located behind
terminal strip X50 at the back of the
connection array. It monitors the com-
pressor power supply feed.
Two versions may be used.
The following alternatives are set up
in the delivered condition:
Over/undervoltage
15 %
Phase asymmetry
15 %
Switching delay
4 s
Remove the cause if the relay
responds. The relay does not need to
be reset.
Fuse
(cont.)
127
Components
55
92
901
GB
Service