Standard setting
100
Setting range
5 to 1000
Excessive room temperature
Prerequisite: Room temperature sen-
sor installed and enabled (see
page 105).
If the temperature captured by the
room temperature sensor exceeds the
set room temperature by the value
selected here, all room heating com-
ponents (heat pump, electric heater
and possibly an external heat source)
are switched OFF.
Access
&
"
System settings
"
&
"
Program
"
&
"
Heating circuit
"
&
"
Heating circuit 1/2
"
&
"Room T excess "
(
1
/
!
)
Standard setting
5 K
Setting range
0 to 20 K
Excessive flow temperature
This function selects the temperature
rise of the secondary circuit over that
of the mixer circuit, subject to a mixer
circuit being connected.
Access
&
"
System settings
"
&
"
Program
"
&
"
Heating circuit
"
&
"
Heating circuit 2
"
&
"T flow excess "
(
1
/
!
)
Standard setting
0 K
Setting range
-10 to 40 K
Mixer runtime
Setting of the time required by the ser-
vomotor of the external heating circuit
mixer for a
complete changeover
from one operating state into another
(90 degree movement).
Runtimes that are too short can lead
to the heating circuit mixer "Cycling".
Access
&
"
System settings
"
&
"
Program
"
&
"
Heating circuit
"
&
"
Heating circuit 2
"
&
"Mixer runtime"
(
0
/
=
)
Standard setting
0:10 min
Integral room temperature controller
(cont.)
108
Heating circuit control settings
55
92
901
GB
Содержание VITOCAL 300
Страница 19: ...Connection diagram Open CLOSE System version 1 cont 19 Preparing for installation 5592 901 GB...
Страница 22: ...Connection diagram Open CLOSE System version 2 cont 22 Preparing for installation 5592 901 GB...
Страница 66: ...Main menu Information A See page 67 Menu structure overview Information 66 Control unit settings 5592 901 GB...
Страница 137: ...Control PCB 137 Connection and wiring diagrams 5592 901 GB Service...
Страница 140: ...Parts lists cont 140 Parts lists 5592 901 GB...
Страница 141: ...Parts lists cont 141 Parts lists 5592 901 GB Service...
Страница 159: ...159 5592 901 GB...