76
Coding in the delivered condition
Possible change
Weather-compensated/room temperature hook-up
b0:0
With remote control:
Heating mode/reduced
mode: weather-compen-
sated (only for weather-
compensated control
units; only change the
code for the heating cir-
cuit with mixer)
b0:1
Heating mode: weather-
compensated
Reduced mode: with room
temperature hook-up
b0:2
Heating mode: with room
temperature hook-up
Reduced mode: weather-
compensated
b0:3
Heating mode/reduced
mode: with room tempera-
ture hook-up
Economy function room temperature
b5:0
With remote control: No
room temperature-de-
pendent heating circuit
pump logic function (only
for weather-compensa-
ted control units; only
change the code for the
heating circuit with mix-
er)
b5:1
to
b5:8
Heating circuit pump logic
function, see the following
table:
Parameter ad-
dress b5:...
With heating circuit pump logic function:
Heating circuit pump "OFF"
Heating circuit pump "ON"
1
RT
actual
> RT
set
+ 5 K
RT
actual
< RT
set
+ 4 K
2
RT
actual
> RT
set
+ 4 K
RT
actual
< RT
set
+ 3 K
3
RT
actual
> RT
set
+ 3 K
RT
actual
< RT
set
+ 2 K
4
RT
actual
> RT
set
+ 2 K
RT
actual
< RT
set
+ 1 K
5
RT
actual
> RT
set
+ 1 K
RT
actual
< RT
set
6
RT
actual
> RT
set
RT
actual
< RT
set
- 1 K
7
RT
actual
> RT
set
- 1 K
RT
actual
< RT
set
- 2 K
8
RT
actual
> RT
set
- 2 K
RT
actual
< RT
set
- 3 K
Coding in the delivered condition
Possible change
Min. flow temperature heating circuit
C5:20
Electronic minimum flow
temperature limit 20 °C
(only for weather-com-
pensated control units)
C5:1
to
C5:127
Minimum limit adjustable
from 1 to 127 °C (limited by
boiler-specific parameters)
Code 1
Heating circuit 1, heating circuit 2, heating…
(cont.)
5623 520 GB