173
Setting and actual values
Set value Commis-
sioning
Mainte-
nance/
Service
Date
Signature
Static pressure
mbar
≤ 57.5
Supply pressure (flow pres-
sure)
=
for natural gas E
mbar
17.4-25
=
for natural gas LL
mbar
17.4-25
=
for LPG
mbar
42.5-57.5
Tick gas type
Carbon dioxide content
CO
2
for natural gas
■ At lower heating output
% by vol.
7.5-9.6
■ At upper heating output
% by vol.
7.5-9.6
For LPG
■ At lower heating output
% by vol.
9.0-11.3
■ At upper heating output
% by vol.
9.0-11.3
Oxygen content O
2
■ At lower heating output
% by vol.
3.8-7.3
■ At upper heating output
% by vol.
3.8-7.3
Carbon monoxide content
CO
■ At lower heating output
ppm
< 1000
■ At upper heating output
ppm
< 1000
Commissioning/service reports
5623 520 GB
Service
Содержание Series B2HA 40