70
Select
"Boiler"
for weather-compensated control units (see page 66).
Select
"2"
for constant temperature control units (see page 66).
Coding
Coding in the delivered condition
Possible change
Single/multi boiler system
01:1
Single boiler system (only
for constant temperature
control units)
01:2
Multi boiler system with
Vitotronic 300-K
Boiler number
07:1
Boiler number in multi
boiler systems (only for
constant temperature
control units)
07:2
to
07:8
Boiler number 2 to 8 in mul-
ti boiler systems
Burner service in 100 hours
21:0
No service interval (hours
run) selected
21:1
to
21:100
Number of hours run be-
fore the burner should be
serviced is adjustable from
100 to 10,000 h
One adjusting step
≙
100 h
Service interval in months
23:0
No time interval for burn-
er service
23:1
to
23:24
Interval adjustable from 1
to 24 months
Service status
24:0
No
"Service"
display
24:1
"Service"
display (the ad-
dress is automatically set
and must be manually re-
set after a service has been
carried out)
Filling/Venting
2F:0
Venting program/fill pro-
gram disabled
2F:1
Venting program enabled
2F:2
Fill program enabled
DHW/group "3"
Select
"DHW"
for weather-compensated control units (see page 66).
Select
"3"
for constant temperature control units (see page 66).
Code 1
Boiler/group "2"
5623 520 GB