88
Coding in the delivered condition
Possible change
7b:1
With LON communication
module: Control unit
transmits the time (only
for weather-compensa-
ted control units)
7b:0
Does not transmit time
7F:1
Detached house (only for
weather-compensated
control units)
7F:0
Apartment building
Separate adjustment of
holiday program and time
program for DHW heating
possible.
80:6
If a fault occurs for at least
30 s, a fault message is
displayed
80:0
Immediate fault message
80:2
to
80:199
Minimum fault duration un-
til fault message occurs,
adjustable from 10 s to
995 s; 1 step
≙
5 s
81:1
Automatic summer/win-
tertime changeover
81:0
Manual summer/winter-
time changeover
81:2
Use of the radio clock re-
ceiver (automatic recogni-
tion)
81:3
With LON communication
module: The control unit re-
ceives the time
82:0
Operation with natural
gas
82:1
Operation with LPG (only
adjustable if coding ad-
dress 11:9 has been set)
88:0
Temperature display in
°C (Celsius)
88:1
Temperature display in °F
(Fahrenheit)
8A:175
Do not adjust.
8F:0
Operation in the standard
menu and extended
menu enabled.
Note
The respective code is
only activated when you
exit the service menu.
8F:1
Operation in the standard
menu
and
extended menu
blocked.
Emissions test mode can
be enabled.
8F:2
Operation enabled in the
standard menu; blocked in
the extended menu.
Emissions test mode can
be enabled.
Code 2
General/group "1"
(cont.)
5623 520 GB
Содержание Series B2HA 40
Страница 16: ...16 3 2 2x 1 4 4x 5 Installation sequence Opening the control unit casing cont 5623 520 GB ...
Страница 172: ...172 0002 0001 0003 0005 0004 Parts lists Miscellaneous cont 5623 520 GB ...
Страница 178: ...178 5623 520 GB ...