54
Parameter
Setting
"System definition"
■
"System scheme 7000"
"6"
■
"External extension 7010"
"1"
■
"Common flow temperature sensor system
701B"
"1"
"Cooling"
■
"Cooling 7100"
"3"
■
"Cooling circuit 7101"
"4"
DHW heating:
"Time program DHW"
Set time program (see oper-
ating instructions)
"Time prog. DHW circ."
Set time program (see oper-
ating instructions)
"DHW"
■
"Enable booster heaters for DHW heating 6014" "1"
"Electr booster heater"
"Enable instantaneous heating water heater 7900" "1"
If required,
"Enable instant. heating water heater for
central heating 7902"
"1"
"Output for instant. heating water heater at power-
OFF 790A"
■
"1"
for 3 kW
■
"2"
for 6 kW
■
"3"
for 9 kW
"Heating water buffer cylinder"
■
"Enable buffer cylinder / low loss header 7200"
"1"
Remote control units
:
"Heating circuit 1"
■
"Remote control 2003"
"1"
"Heating circuit 2"
■
"Remote control 3003"
"1"
System example 3, ID: 4605352_1008_01
Note
Type BW 301.A is shown. In types BWC
301.A and WWC 301.A, the circulation
pumps (primary pump, secondary pump
and circulation pump for cylinder heat-
ing) are installed and connected at the
factory.
Setting system scheme 10
■ Single stage heat pump, type BW
301.A
■ 1 heating circuit without mixer (A1)
■ 2 heating circuits with mixer (M2, M3)
■ External heat source for heating and
DHW
■ DHW heating with solar backup
Preparing for installation
System example 2, ID: 4605351_1008_01
(cont.)
5600 161 GB
Содержание BW 01.A06
Страница 65: ...65 Removing the top panel 1 Installation sequence Siting the heat pump cont 5600 161 GB Installation ...
Страница 121: ...121 Opening the shield Troubleshooting Repairs cont 5600 161 GB Service ...
Страница 122: ...122 Overview of internal components M C D F E B G O N K P A J I L Troubleshooting Repairs cont 5600 161 GB ...
Страница 166: ...166 5600 161 GB ...
Страница 167: ...167 5600 161 GB ...