Phase monitor (if installed)
The phase monitor is used to monitor the
mains power supply to the compressor.
The following different mains supplies (if
adjustable) are permissible in the deliv-
ered condition:
Over/undervoltage
15 %
Phase asymmetry
15 %
Switching delay
4 s
The phase monitor switches off (switch-
ing contact opens) if these tolerances
are exceeded.
The phase monitor automatically re-ena-
bles the power supply if the values return
to within the specified tolerance range.
Remove the cause if the relay has
responded. The relay does not need to
be reset.
Version 1
A
H
B
C
G
F
E
D
D
<>U
A1
Asy
Ph
Rel
A2
L1
L2
L3
14
11
12
<>U
Asy
t
2
4
12
%
15
10
5
%
20
10
6
0.1
A
Over/undervoltage in %
B
Phase asymmetry in %
C
Switching delay in s
D
Contact used in safety chain (N/O)
E
ON/OFF indicator ("Rel")
F
Fault display phase failure/phase
sequence ("Ph")
G
Fault display asymmetry ("Asy")
H
Fault display over/undervoltage
("<>U")
LEDs explained
■ LED "Rel" illuminates green:
All voltages and the rotating field
(clockwise) are healthy.
■ LED "Ph" illuminates red:
The relay has responded; the rotating
field is anticlockwise.
■ All LED's off:
One or several phases have dropped
out.
■ LED "<>U" illuminates red:
Incorrect voltage on one/several
phase(s).
■ LED "Asy" illuminates red:
Asymmetry on one/several phase(s).
Installation sequence
Power supply
(cont.)
5600 161 GB
Installation
Содержание BW 01.A06
Страница 65: ...65 Removing the top panel 1 Installation sequence Siting the heat pump cont 5600 161 GB Installation ...
Страница 121: ...121 Opening the shield Troubleshooting Repairs cont 5600 161 GB Service ...
Страница 122: ...122 Overview of internal components M C D F E B G O N K P A J I L Troubleshooting Repairs cont 5600 161 GB ...
Страница 166: ...166 5600 161 GB ...
Страница 167: ...167 5600 161 GB ...