114
Two-stage heat pump
Parameter
Setting
Compressor 2:
■
"Enable compressor 5100"
"1"
■
"Output compressor stage 2 5130"
Value corresponding to the
rated heating output of heat
pump stage 2, see type
plate
External functions
External functions
Parameter
Setting
External demand
Poss.
"Internal hydraulics"
Ó
"Flow temperature for
external demand 730C"
Set flow temperature
for external demand
External starting of the com-
pressor; mixer in control
mode or OPEN
"System definition"
Ó
"Effect of external demand
on heat pump/heating cir-
cuits 7014"
"0"
to
"7"
(Observe parameter
"Flow temperature
for external demand
730C"
)
External changeover of the
operating mode of various
system components
"System definition"
Ó
"System components for
external changeover
7011"
"0"
to
"10"
"System definition"
Ó
"Operating status for
external changeover
7012"
"0"
to
"3"
"System definition"
Ó
"Duration of external
changeover 7013"
"0"
to
"12"
External blocking of compres-
sor and pumps
"System definition"
Ó
"Effect of external block-
ing on pumps/compressor
701A"
"0"
to
"31"
Commissioning, inspection, maintenance
Further details regarding the individual steps
(cont.)
5600 161 GB
Содержание BW 01.A06
Страница 65: ...65 Removing the top panel 1 Installation sequence Siting the heat pump cont 5600 161 GB Installation ...
Страница 121: ...121 Opening the shield Troubleshooting Repairs cont 5600 161 GB Service ...
Страница 122: ...122 Overview of internal components M C D F E B G O N K P A J I L Troubleshooting Repairs cont 5600 161 GB ...
Страница 166: ...166 5600 161 GB ...
Страница 167: ...167 5600 161 GB ...