67
Connecting the secondary circuit
1.
Equip the secondary circuit on site
with an expansion vessel and safety
assembly (in accordance with
DIN 4757).
Fit the safety assembly to the on-site
line in the heating water return.
2.
Connect secondary lines to heat
pump (
7
≥
28 mm).
!
Please note
To prevent equipment dam-
age,
connect on-site secondary
lines to the heat pump so that
they are free of load and tor-
que stresses.
!
Please note
Make tight hydraulic connec-
tions on the secondary side.
In the case of hose outlets,
ensure diaphragm grommets
are seated correctly. If neces-
sary, seal with sealing tape.
3.
Fill and vent secondary circuit.
4.
Thermally insulate pipes inside the
building.
Note
■ For diaphragm grommets, see
■ In underfloor heating circuits, integrate
a temperature limiter on site for limiting
the maximum temperature of under-
floor heating systems.
■ Safeguard minimum flow rate, e.g.
with overflow valve (see Specification
on page 152).
Installation sequence
Hydraulic connections
(cont.)
5600 161 GB
Installation
Содержание BW 01.A06
Страница 65: ...65 Removing the top panel 1 Installation sequence Siting the heat pump cont 5600 161 GB Installation ...
Страница 121: ...121 Opening the shield Troubleshooting Repairs cont 5600 161 GB Service ...
Страница 122: ...122 Overview of internal components M C D F E B G O N K P A J I L Troubleshooting Repairs cont 5600 161 GB ...
Страница 166: ...166 5600 161 GB ...
Страница 167: ...167 5600 161 GB ...