115
External functions
Parameter
Setting
External blocking of the com-
pressor; mixer in control
mode or CLOSED
"System definition"
Ó
"Effect of external block-
ing on heat pump/heating
circuits 7015"
"0"
to
"8"
"System definition"
Ó
"Effect of external block-
ing on pumps/compressor
701A"
"0"
to
"31"
Central fault message
No parameters need to be
set.
Cooling function
Cooling function parameters
Setting
"Cooling"
Ó
"Cooling function 7100"
■
"0"
(no cooling)
■
"2"
(natural cooling on cooling
circuit without mixer)
■
"3"
(natural cooling on cooling
circuit with mixer)
■
"4"
(active cooling)
"Cooling"
Ó
"Cooling circuit 7101"
■
"1"
(heating circuit A1)
■
"2"
(heating circuit M2)
■
"3"
(heating circuit M3)
■
"4"
(separate cooling circuit)
Instantaneous heating water heater
Parameters for
Instantaneous heating water heater
Setting
"Electr booster heater"
Ó
"Enable instantaneous heating water heater
7900"
"1"
Poss.
"Electr booster heater"
Ó
"Enable instant. heating water heater for cen-
tral heating 7902"
"1"
"Electr booster heater"
Ó
"Output for instant. heating water heater at
power-OFF 790A"
■
"1"
for 3 kW
■
"2"
for 6 kW
■
"3"
for 9 kW
Poss.
"DHW"
Ó
"Enable electric heaters for DHW heating
6015"
"1"
Commissioning, inspection, maintenance
Further details regarding the individual steps
(cont.)
5600 161 GB
Service
Содержание BW 01.A06
Страница 65: ...65 Removing the top panel 1 Installation sequence Siting the heat pump cont 5600 161 GB Installation ...
Страница 121: ...121 Opening the shield Troubleshooting Repairs cont 5600 161 GB Service ...
Страница 122: ...122 Overview of internal components M C D F E B G O N K P A J I L Troubleshooting Repairs cont 5600 161 GB ...
Страница 166: ...166 5600 161 GB ...
Страница 167: ...167 5600 161 GB ...