112
Pumps and other components
Pump/component
Parameter
Setting
Secondary pump (for
heating circuit A1 without
heating water buffer cyl-
inder; no additional heat-
ing circuit pump
required)
"System definition"
Ó
"System scheme 7000"
"1"
to
"11"
Heating circuit pump A1
(in conjunction with heat-
ing water buffer cylinder
in addition to the secon-
dary pump)
"System definition"
Ó
"System scheme 7000"
With heating circuit A1 (for
heating circuit without mixer
A1)
Heating circuit pump and
mixer M2
"System definition"
Ó
"System scheme 7000"
With heating circuit M2 (for
heating circuit with
mixer M2)
Heating circuit pump and
mixer M3 (control via
extension kit for one
heating circuit with
mixer)
"System definition"
Ó
"System scheme 7000"
With heating circuit M3 (for
heating circuit with mixer
M3)
Note
Set rotary switch S1 in the
extension kit to "2" (see
extension kit installation
instructions).
Circulation pump for cyl-
inder heating
"System definition"
Ó
"System scheme 7000"
With DHW heating
"Internal hydraulics"
Ó
"Enable three-way
diverter valve heating/
DHW 730D"
"0"
DHW heating
with primary store sys-
tem:
■ Cylinder primary pump
■ 2-way shut-off valve
"External heat source"
Ó
"Enable external heat
source for DHW heating
7B0D"
"1"
"System definition"
Ó
"System scheme 7000"
With DHW heating
DHW circulation pump
Extended menu:
"Time prog. DHW circ."
Setting a time program
Commissioning, inspection, maintenance
Further details regarding the individual steps
(cont.)
5600 161 GB
Содержание BW 01.A06
Страница 65: ...65 Removing the top panel 1 Installation sequence Siting the heat pump cont 5600 161 GB Installation ...
Страница 121: ...121 Opening the shield Troubleshooting Repairs cont 5600 161 GB Service ...
Страница 122: ...122 Overview of internal components M C D F E B G O N K P A J I L Troubleshooting Repairs cont 5600 161 GB ...
Страница 166: ...166 5600 161 GB ...