83
Central fault message
223.1
L1
230 V~, 0.5 A
N
223.2
A
A
Terminals on extension PCB
Plug
sXF
Terminals
Function
Explanation
224.2
2.
Primary pump for heat pump
stage 2 (if installed)
Connection values
■ Output: 200 W
■ Voltage: 230 V~
■ Max. switching current: 4(2) A
Connect on site.
224.3
2.
Secondary pump for heat
pump stage 2 (if installed)
Connection values
■ Output: 130 W
■ Voltage: 230 V~
■ Max. switching current: 4(2) A
Connect on site.
224.4
r
2.
Control of instantaneous
heating water heater,
stage 2
Connection values
■ Output: 10 W
■ Voltage: 230 V~
■ Max. switching current: 4(2) A
Connect on site.
224.5
2.
Circulation pump for cylinder
heating (on the heating
water side) for heat pump
stage 2 (if installed)
Connection values
■ Output: 130 W
■ Voltage: 230 V~
■ Max. switching current: 4(2) A
Connect on site.
Installation sequence
Electrical connections
(cont.)
5600 161 GB
Installation
Содержание BW 01.A06
Страница 65: ...65 Removing the top panel 1 Installation sequence Siting the heat pump cont 5600 161 GB Installation ...
Страница 121: ...121 Opening the shield Troubleshooting Repairs cont 5600 161 GB Service ...
Страница 122: ...122 Overview of internal components M C D F E B G O N K P A J I L Troubleshooting Repairs cont 5600 161 GB ...
Страница 166: ...166 5600 161 GB ...
Страница 167: ...167 5600 161 GB ...