9. Appliance installation. 

Trained  and  competent  technicians  or  companies  must  perform  the  installing  a  pellet  stove!  Qualified  technicians 
should perform all  activities  in  inspection  and  repair  of  electrical components. Switch  off the pellet  stove  from the 
electric supply before any inspection or repair! 

Refer  to  the  regulations  valid  for  the  country,  where  the  pellet  stove  will  be  used,  if  you  do  not  find  the information  you  are 
interested in this instruction manual.  

It is not recommended to install a pellet stove in rooms where there is mounted another heater. If it does, it must be equipped 
with a separate air duct. 

Compatibility with other devices: 

Pellet stove should not be installed in the same room in which there are absorbers and / or devices that reduce ventilation in the 
room. 

Checking electrical connections: 

Pellet stove is equipped with a power cable to be connected to a voltage 230V / 50Hz. Changes exceeding by 10% the voltage can 
damage  the  appliance.  Electrical  grid-circuit  must  comply  with  the  provisions  of  the  laws  and  requirements  for  grounding. 
According to the requirements for electrical grid-circuit connection, pellet stove should be installed so as to ensure free access to 
the plug and socket (230V / 50Hz). According to the safety requirements it’s prohibited the room where the pellet stove is installed 
to have electrical installation mounted on the floor. Lack of bonding / grounding can cause damage for which the manufacturer is 
not responsible. 

Positioning: 

To ensure well operation, pellet stove should be leveled. The floor on which is placed the pellet stove must be of non-combustible 
materials (concrete, marble, terracotta, etc.)  

Given the easy servicing and refueling, we recommend the following minimum free distance around the pellet stove: 1000 mm at 
the front, back and sides -500 mm, top -minimum 1000 mm. 

Safe distances for fire safety: 
When installing a pellet stove and storage of wood pellets must be respected the fire requirements! 

It is recommended that an appropriate place to mount a fire extinguisher be ensured.  

It is forbidden to store the wood pellets directly to the pellet stove or a distance of less than 400 mm. 

The optimal distance between the pellet stove and combustible materials is 800mmin front and 300 mm from the sides and the 
back. Inflammable objects should not be placed on the top board of the pellet stove. 

If the chimney is connected to the timber wall or other inflammable material, suitable materials such as ceramic wool  should be 
used to isolate it. 

Fresh air opening:  

Imperative to ensure submission of fresh air! 
 

The room, in which is mounted pellet stove must have an opening for fresh air with a cross section of not less than 80 cm² in order 
to ensure a sufficient supply of oxygen necessary for combustion. Additionally, it can be delivered outside air through a steel pipe 
of Ø 50 mm. In this case, it is possible to emerge condensate. If necessary, the opening for external air can be protected by a grid 
whose light-section should not be less than 12 cm². Pipe for outside air has to be mounted on the nearest outer wall to the pellet 
stove. Its length should not exceed 1 m, should not have curves and its location has to prevent clogging. The outer end of the pipe 
must end with a knee 90˚, downward or be provided with protection against wind. 

Chimneys: 

Pellet stove works constantly with a fume extractor and pressure in the flue pipes and chimney. 

It is forbidden flue gases to be discharged directly from the pellet stove through the wall into the atmosphere. Required installed 
chimney, which takes flue gases safe for human health altitude over the area of habitation. 

Only the pellet stove should use chimney and no other appliances have to be connected to it. The flue gases are emitted from the 
combustion chamber of the pellet stove to the atmosphere through a flue socket Ø 80 mm located in the rear. It is recommended 
at the beginning of the vertical section of the chimney to mount a T-fitting, with a section for collecting condensate. Pellet stove 
must be connected to the chimney by steel flue pipes, certified according to EN 1856. The flue pipe system must be hermetically 
insulated with materials resistant to high temperatures (heat-resistant silicone or grease). Allowed to have a horizontal section 
with a length of 2 m. Horizontal section must be a minimum slope of 3% and not more than two curves at 90°. 

If the flue socket of the pellet stove is connected to a metal chimney, it must have a vertical portion length of not less than 1.5 m 
and fitted with a wind protection. Chimney may be located internally or externally. It should be well insulated. 

If the pellet stove is connected to a masonry chimney, it must be intended for appliances for solid fuel. If the chimney has a size 
larger from Ø150 mm in diameter, internally along its entire length must be installed tube of stainless steel with a diameter of 
Ø150 mm, as the free space has to be isolated by masonry. All parts of the chimney should have free access to inspection. At the 

Содержание VITTORIA 10

Страница 1: ...INSTRUCTION MANUAL for installation and operation of air pellet stove VITTORIA 8 VITTORIA 10...

Страница 2: ...E CONTROL UNIT 10 10 2 3 MAIN MENU 11 10 2 4 INSTALLER SETTINGS 12 10 2 5 SERVICE TECHNICIAN SETTINGS 13 10 3 COLD TEST 14 11 INSTRUCTION MANUAL 14 11 1 WOOD PELLETS LOADING 14 11 2 WOOD PELLET REFUEL...

Страница 3: ...of failure of any of its components Safety components are activated without outside interference Necessary for the proper operating of the pellet stove is its proper installation in accordance with t...

Страница 4: ...Victoria 05 Ltd 4 3 Technical data and dimensions Drawing 1...

Страница 5: ...pellets with calorific value not less than 4300 ccal kg and heat loss of heated room 33 ccal m h Consideration must be given to the availability of external devices that can influence the operation o...

Страница 6: ...outlet and intakes combustion air by vacuum Gear motor Driven auger screw by means of which the pellets are conveyed from the pellet fuel hopper to the combustion chamber Room air fan Ensures additio...

Страница 7: ...from Picture 2 Through the control panel the user can visualize and manage all stages of the operation of the pellet stove 8 Fuel Pellet stove e designed and programmed to burn wood pellets They have...

Страница 8: ...o the timber wall or other inflammable material suitable materials such as ceramic wool should be used to isolate it Fresh air opening Imperative to ensure submission of fresh air The room in which is...

Страница 9: ...after installation to make a detailed instruction of the user Pellet stove is coated by high temperature resistant paint but not against corrosion In case of accumulation of dust surfaces can be clean...

Страница 10: ...appear after the process has been finished If for more than 6 seconds there is no connection to the Control Unit the value will not be saved Day time and night time temperatures To change the require...

Страница 11: ...h Intermediate clean indicates the time left before the system starts cleaning mode Recommended value 600 Pellets indicates the volume of the pellets used during operation mode Input value is gr min D...

Страница 12: ...have to be touched to unlock the display 10 2 4 Installer settings Types of settings for Installer entered with installer password Factory settings Vittoria 8 Vittoria 10 Duration 700 sec 700 sec Fan...

Страница 13: ...s how often the cleaning procedure has to be triggered The set value is summed up from the feed screw working time By this way it s possible to set the cleaning based on the calculation of the amount...

Страница 14: ...me runs out the mode is changed to feeding loading In this mode again a time counter is shown The default time is 70 sec The smoke fan is reducing the power The screw is activated and starts loading i...

Страница 15: ...ny scales that clog the holes Picture 6 Vacuum clean the combustion chamber and all contact edges Clean the glass when it is cold If necessary use appropriate detergent Never vacuum hot coals because...

Страница 16: ...as stopped working Error messages are described below Do not unplug the pellet stove from the main electrical supply during shutdown process In case of failure To restart the pellet stove is necessary...

Страница 17: ...pipes and combustion chamber are clean Flue outlet pipes are clean 15 Frequently Asked Questions The following answers are tentative For more details use the instruction manual What is need to prepare...

Страница 18: ...f the pellet stove has not worked for a long time Can you use other types of fuel than wood pellets NO Pellet stove is designed to work with wood pellets with a diameter of 6 mm The use of another typ...

Страница 19: ...12 2018 INSTRUCTION MANUAL for installation and operation of pellet stove VITTORIA 8 VITTORIA 10 19...

Страница 20: ...Victoria 05 Ltd 20...

Страница 21: ...12 2018 INSTRUCTION MANUAL for installation and operation of pellet stove VITTORIA 8 VITTORIA 10 21...

Страница 22: ...Victoria 05 Ltd 22...

Страница 23: ...12 2018 INSTRUCTION MANUAL for installation and operation of pellet stove VITTORIA 8 VITTORIA 10 23...

Страница 24: ...ass sealing set 11 Combustion chamber set 12 Fire grate 13 Deflector top 14 Handle 15 Fire door set 16 Ashtray 17 Grill for hopper 18 Left side plate set 19 Right side plate set 20 Special tool 21 Dis...

Страница 25: ...the remaining population For other countries please contact you dealer Any warranty repair of the pellet stove is recorded in the diary of warranty Warranty of the pellet stove is NOT VALID in the fol...

Страница 26: ...Victoria 05 Ltd 26 DIARY for repairs under warranty Company Receipt date Type of repair Delivery date Carried out...

Страница 27: ...12 2018 INSTRUCTION MANUAL for installation and operation of pellet stove VITTORIA 8 VITTORIA 10 27...

Страница 28: ...Victoria 05 Ltd 1B Ivan Momchilov Str 5100 Gorna Oryahovitsa Republic of Bulgaria phone 359 618 60282 fax 359 618 60200 e mail info v05 bg http www v05 bg...

Отзывы: