Victoria-05 Ltd.
14
Indoor fan- we can choose between 1%to 100%.Choosing from 1 to 100
and then safe, at the exit of the indoor fan OUT3 is triggered
modulation of the power.
10.3. Cold test.
The cold test is necessary to check the working order and proper connection of electrical components in the pellet stove. The test
of the outputs is possible only in ready mode. When going into starting mode the test it terminated. To perform Cold test is
necessary to go into “output test” menu and test all five components.
11. Instruction manual.
11.1. Wood pellets loading.
The capacity of the pellet fuel hopper is 24 kg. The opening for charging the hopper is with dimensions 167 х 300 mm.
If the hopper is left without pellets, the pellet stove will stop working and „Fire extinct“ alarm will be shown on the display.
11.2. Wood pellet refueling.
When the pellet fuel hopper is completely empty, it means that the screw auger is also empty. Before re-ignite the pellet stove, it
is necessary to load it with wood pellets.
During initial igniting of the pellet stove or during igniting of the stove after the pellet hopper was empty, it is possible the startup
procedure to be repeated. It is possible that sometimes few pellets to be left in the hopper. Once a month the user has to clean
the pellet hopper with vacuum cleaner in order to avoid clogging with dust and particles.
11.3. Starting up the system.
To start up the system it is necessary to hold for 3 seconds the startup icon, this will be additionally indicated with sound
notification. To stop the system it is necessary to hold for 3 seconds the flame icon. The stove will change the mode to cleaning
and stand by.
During staring up the controller is initially checking the sensor for the flue gas temperature. If the temperature is above the set, it
is shifting directly to modulation. If it is not, the controller is checking is there any interruption of it during any of the modes. If
there was such interruption, the restart alarm is shown of the controller and its shifting to the appropriate mode where the
interruption has been detected.
If there was not such interruption and the temperature sensor is under the set temperature, the sign Stand-by is changed to Start
and counter is shown. In this mode is triggered the initial cleaning process which by default is 60 sec. The smoke fan is at maximum
power in order to clean the combustion chamber. If we like, the time duration can be changed from Cleaning menu.
After the time runs out the mode is changed to feeding/loading. In this mode, again a time counter is shown. The default time is
70 sec. The smoke fan is reducing the power.
The screw is activated and starts loading in the following timing: 2 seconds loading, 3 seconds hold.
The ignition is started.
In this mode, the working time can be adjusted. By adjusting it, it is possible to determinate the quantity of the pellets. The
adjustment can be made in menu Ignition/ Initial loading
After the time runs out the stove is going into ignition mode. The ignition remains on. It is now possible to adjust the feeding and
hold interval of the screw. The screw will remain operational.
Adjusting of the parameters is made through menu igniting/screw feed/screw interval.
This is temporary mode. To get thru the next mode its necessary the temperature sensor to detect rising of the
temperature above the set in the ignition/flame sensor menu. The higher value has to be kept for more than 10 seconds!
If there is failure to do that and the time runs out, the controller is triggering second pellet loading with the respective set time
adjustable thru menu ignition/second loading.
If everything is correct the controller shifts to warming up mode. The purpose of this mode is to fire up the pellets very good and
stabilizing the flame. The parameters of this process are adjustable in menu warming up.
After warming up mode, the stove is shifting to Modulations mode. The first is P3, next is P2 and last is P1. Shifting between the
modulations depends from the set temperature. For example, if the set temperature is 30°С:
-
in menu Р3/ Temperature difference is set 3°С;
-
in menu Р2/Temperature difference is set 1°С;
-
in menu Р1/Temperature difference is set 1°С.
With these settings, the working process will be as follows:
-
when temperature of 27°С is reached, which is 3°Сlower than the set, the modulation will shift to Р2;
-
when temperature of 29°Сis reached, which is 1°Сlower than the set, the modulation will shift to Р1;
-
when temperature of 31°Сis reached, which is 1°Сabove the set, the modulation will shift to STOP.
In stopping mode, cleaning procedure is started during extinguishing. In this mode, the control unit is waiting for drop of the
temperature with 2°С, in the example to 28°С. After the low temperature is detected, the startup process is triggered.
When the set time for cleaning during stopping procedure runs out, the control unit shifts to ECO mode. In ECO mode two very
important conditions have to be completed:
-
first is to run out the set time of 600 seconds;
-
after that, checkup is made is the ambient temperature below the set.
When these two conditions are completed the control unit shifts to start up procedure.
Содержание VITTORIA 10
Страница 1: ...INSTRUCTION MANUAL for installation and operation of air pellet stove VITTORIA 8 VITTORIA 10...
Страница 4: ...Victoria 05 Ltd 4 3 Technical data and dimensions Drawing 1...
Страница 19: ...12 2018 INSTRUCTION MANUAL for installation and operation of pellet stove VITTORIA 8 VITTORIA 10 19...
Страница 20: ...Victoria 05 Ltd 20...
Страница 21: ...12 2018 INSTRUCTION MANUAL for installation and operation of pellet stove VITTORIA 8 VITTORIA 10 21...
Страница 22: ...Victoria 05 Ltd 22...
Страница 23: ...12 2018 INSTRUCTION MANUAL for installation and operation of pellet stove VITTORIA 8 VITTORIA 10 23...
Страница 27: ...12 2018 INSTRUCTION MANUAL for installation and operation of pellet stove VITTORIA 8 VITTORIA 10 27...