VTR73xxA Terminal Equipment Controller Specifications  

 

 

Terminal Equipment Controller power requirements:  7.0 Vdc +/- 10% 2.4 watts minimum 

Operating conditions:  0 °C to 50 °C ( 32 °F to 122 °F ) 

  0% to 95% R.H. non-condensing 

Storage conditions:  -30 °C to 50 °C ( -22 °F to 122 °F ) 

  0% to 95% R.H. non-condensing 

Temperature sensor:  Local 10 K NTC thermistor 

Temperate sensor resolution:  ± 0.1 °C   ( ± 0.2 °F ) 

Temperature control accuracy:  ± 0.5 ° C  ( ± 0.9 °F ) @ 21 °C ( 70 °F ) typical calibrated 

Humidity sensor and calibration:  Single point calibrated bulk polymer type sensor 

Humidity sensor precision:  Reading range from 10-90 % R.H. non-condensing 

10 to 20% precision is 10% 
20% to 80% precision is 5% 
80% to 90% precision is 10% 

Humidity sensor stability  Less than 1.0 % yearly (typical drift) 

Dehumidification setpoint range:  30% to 95% R.H. 

Occ, Stand-By and Unocc cooling setpoint range:  12.0 to 37.5 °C ( 54 to 100 °F ) 

Occ, Stand-By and Unocc heating setpoint range:  4.5 °C to 32 °C ( 40 °F to 90 °F ) 

Room and outdoor air temperature display range  -40 °C to 50 °C ( -40 °F to 122 °F ) 

Proportional band for room temperature control:  Cooling & Heating: Default: 1.8°C ( 3.2°F ) 

Binary inputs:  Dry contact across terminal BI1, BI2 & UI3 to Scom 

Wire gauge  14 gauge maximum, 22 gauge recommended 

Dimensions: 4.94” 

x 3.38” x 1.13” 

Approximate shipping weight:  0.75 lb ( 0.34 kg ) 

 

(PENDING)

 Agency Approvals all models: 

UL:

 UL 873 (US) and CSA C22.2 No. 24 (Canada), File E27734 

with CCN XAPX (US) and XAPX7 (Canada) 

 

Industry Canada: 

ICES-003 (Canada) 

 

(PENDING)

 Agency Approvals all models 

FCC: 

Compliant to CFR 47, Part 15, Subpart B, Class A (US) 

 

CE: 

EMC Directive 89/336/EEC (Europe Union) 

 

C-Tick: 

AS/NZS CISPR 22 Compliant (Australia / New Zealand) 

Supplier Code Number N10696 

(PENDING)

 Agency Approvals Wireless models 

FCC: 

Compliant to: Part 15, Subpart C 

THIS DEVICE COMPLIES WITH PART 15 OF THE FCC RULES. OPERATION IS SUBJECT TO THE FOLLOWING TWO 
CONDITIONS: (1) THIS DEVICE MAY NOT CAUSE HARMFUL INTERFERENCE, AND (2) THIS DEVICE MUST ACCEPT 
ANY INTERFERENCE RECEIVED, INCLUDING INTERFERENCE THAT MAY CAUSE UNDESIRED OPERATION.

 

 

Drawing & Dimensions  

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

Fig.13 – Terminal Equipment Controller dimensions 

 

 

Important Notice  

 

 

All VTR7300 series 
controls are for use as 
operating controls only 
and are not safety 

devices.  These instruments have 
undergone rigorous tests and 
verifications prior to shipment to 
ensure proper and reliable operation in 
the field.  Whenever a control failure 
could lead to personal injury and/or 
loss of property, it becomes the 
responsibility of the user / installer / 
electrical system designer to 
incorporate safety devices ( such as 
relays, flow switch, thermal 
protections, etc…) and/or alarm 
system to protect the entire system 
against such catastrophic failures. 

 

Tampering of the devices or miss 
application of the device will void 
warranty.

 

 

 

Содержание VTR73 Series

Страница 1: ...000 Series Line Voltage Switching Transformer Relay Pack s operate as slave unit s under the control of a single master VTR73XX Terminal Equipment Controller A single VTR73XX Terminal Equipment Contro...

Страница 2: ...el dependent The VC3xxxX Relay Pack supplies power to the wall VTR73xxA Terminal Equipment Controller The VTR73xxA Controller operates the VC3xxxX Relay Pack s via a simple communication bus A maximum...

Страница 3: ...or is opened any movements detected by the remote PIR sensor or the PIR accessory cover will be ignored Use a Normally Closed contact switching device Contact opened Door opened Contact closed Door cl...

Страница 4: ...ews in mounting holes on each side of the base Fig 4 8 Gently swing back the circuit board on the base and push on it until the tabs lock it 9 1Strip each wire 1 4 inch 10 Insert each wire according t...

Страница 5: ...single VTR73xxA Terminal Equipment Controller From the VTR73xxA Terminal Equipment Controller to the first VC3xxxX Relay Pack o Existing or new field wires o 3 minimum required 14 22 Ga Solid or Stran...

Страница 6: ...conditional to Humidity display is model and configuration dependent Model with RH sensor built in Display function can be enabled with RH display parameter Displayed range is 10 to 90 RH Outdoor air...

Страница 7: ...ertain functions is made with configuration parameter lockout Local Setpoint Adjustment when Stp Func Dual Stp Dual Occupied Setpoints Adjustment Occupied setpoint adjustments Cooling mode Heating mod...

Страница 8: ...t will be strictly for noise comfort issues Auto Speed Fan Mode operation for sequences 2 and 3 is dependent on Auto Fan parameter When Auto Fan is set to AS Default Auto Speed during occupied periods...

Страница 9: ...erminal Equipment Controller reporting to a gateway maximum of 30 Terminal Equipment Controllers per gateway be sure you set the SAME PAN ID value both at the gateway and the Terminal Equipment Contro...

Страница 10: ...tions using a Normally Open NO or Normally Closed NC remote PIR motion sensor Occupancy mode is now set as per applied PIR function and configuration Application information and examples are available...

Страница 11: ...ed Service a backlit flashing Service alarm will be displayed on the Terminal Equipment Controller LCD screen when the input is energized It can be tied in to the AC unit control card which provides a...

Страница 12: ...from 0 to 2 Will enable heat cool operation from the same output 4 0 Pipes can access all the sequences of operation from 0 to 4 Will enable heat cool operation from different output SeqOpera Sequenc...

Страница 13: ...Terminal Equipment Controller unoccupied mode and setpoints become active The factory value or 0 0 hours Setting this parameter to its default value of 0 0 hours disables the unoccupied timer This pre...

Страница 14: ...e permanent ones and saved to EEPROM Permnent permanent Any change of occupied or unoccupied setpoints through the keypad by the user are permanent and saved to EEPROM SptFunc Local setpoint settings...

Страница 15: ...hour under normal control operation It represents the maximum number of cycles that the equipment will turn ON and OFF in one hour Note that a higher C P H will represent a higher accuracy of control...

Страница 16: ...75 lb 0 34 kg PENDING Agency Approvals all models UL UL 873 US and CSA C22 2 No 24 Canada File E27734 with CCN XAPX US and XAPX7 Canada Industry Canada ICES 003 Canada PENDING Agency Approvals all mod...

Отзывы: