3

Configurable BI, RBI, UI, RUI inputs overview  

 

 
BI1, 

Binary input #1 can be configured for the following 

functions: 
 

1. (None): 

No function will be associated with the input 

 

2. (Rem 

NSB):

 remote NSB timer clock input. The 

scheduling will now be set as per the binary input. It 
provides low cost setback operation via a dry contact

 

 

Contact opened = Occupied 

 

Contact closed = Unoccupied 

3.  (Motion NO) and (Motion NC):

 Advanced PIR 

occupancy functions using a Normally Open (NO) or 
Normally Closed (NC) remote PIR motion sensor. 
Occupancy mode is now set as per applied PIR 
function and configuration. Application information and 
examples, are available on document: 

APP-PIR-Guide-

Exx. 

This document will provide the installers and 

system designers with detailed examples on 
applications, parameter configuration information, 
sequence of operation, troubleshooting and diagnostic 
help required for the proper usage of the PIR accessory 
covers

  

4. (Window) 

EMS:

 Forces the system to disable any 

current heating or cooling action by the Terminal 
Equipment Controller. The mode stays the same and 
the current setpoints are the same Occupied setpoints. 
Only the outputs are disabled. There is a Door/Window 
alarm displayed on the Terminal Equipment Controller 
to indicate to the local tenant that the door/window 
needs to be closed for cooling or heating to resume. 
Use NC contact.

 

 

Contact opened = System disabled with local 

Window alarm 

 

Contact closed = System enabled 

 

BI2, 

Binary input #2 can be configured for the following 

functions: 

1. (None): 

No function will be associated with the input 

 

2. 

 (Door Dry) Door contact & Motion detector:

 This 

configuration is only functional if binary input #1 is set 
to 

Motion NO 

or 

Motion NC 

or a 

PIR accessory 

cover

 is used. 

With this sequence enabled, the occupancy is now 
dictated through those 2 inputs. Any motion detected 
will set the zone to occupied status. The zone will 
remain permanently in occupied mode until the door 
contact switch opens momentarily. The Terminal 
Equipment Controller will then go in stand-by mode. If 
more movements are detected, the occupied mode will 
resume. While the door is opened, any movements 
detected by the remote PIR sensor or the PIR 
accessory cover will be ignored. Use a Normally Closed 
contact-switching device. 

 

Contact opened = Door opened 

 

Contact closed = Door closed 

 
RUI1, 

Remote universal input #1 on VC3xxxX can be 

configured for the following functions: 
 

3. (Filter): 

a backlit flashing 

Filter 

alarm will be displayed 

on the Terminal Equipment Controller LCD screen 
when the input is energized. It can be tied to a 
differential pressure switch that monitor filters

  

 

Contact opened = No alarm 

 

Contact closed = Alarm displayed 

 

4. 

(Service): 

a backlit flashing Service alarm will be 

displayed on the Terminal Equipment Controller LCD 
screen when the input is energized. It can be tied in to 
the AC unit control card, which provides an alarm in 
case of malfunction. 

 

Contact opened = No alarm 

 

Contact closed = Alarm displayed 

 

3.  (COC/NH) Change over dry contact. Normally Heat: 

Used for hot

 

/

 

cold water change over switching in 2 

pipe systems. 

 

 

Contact closed = Cold water present 

 

Contact opened = Hot water present 

Only used and valid if system is setup as 2 pipes. 
Parameter ( Pipe No ) set as 2 pipes. 

 

4.   (COC/NC) Change over dry contact. Normally Cool: 

Used for hot

 

/

 

cold water or air change over switching in 

2 pipe systems. 

 

 

Contact closed = Hot water present 

 

Contact opened = Cold water present 

Only used and valid if system is setup as 2 pipes. 
Parameter ( Pipe No ) set as 2 pipes. 

 

5.   (COS) Change over analog sensor: 

Used for hot

 

/

 

cold water or air change over switching in 2 pipe 
systems.

 

Only used and valid if system is setup as 2 pipes. 
Parameter ( Pipe No ) set as 2 pipes. 

 

If temperature is > 77 °F = Hot water present 

 

If temperature is < 75 °F = Cold water present 

 

RBI2, 

Remote binary input #2 on VC3xxxX can be 

configured for the following functions: 
 

1. (Filter): 

a backlit flashing 

Filter 

alarm will be displayed 

on the Terminal Equipment Controller LCD screen 
when the input is energized. It can be tied to a 
differential pressure switch that monitor filters

  

 

Contact opened = No alarm 

 

Contact closed = Alarm displayed 

 

2. 

(Service): 

a backlit flashing Service alarm will be 

displayed on the Terminal Equipment Controller LCD 
screen when the input is energized. It can be tied in to 
the AC unit control card, which provides an alarm in 
case of malfunction. 

 

Contact opened = No alarm 

 

Contact closed = Alarm displayed 

Содержание VTR73 Series

Страница 1: ...000 Series Line Voltage Switching Transformer Relay Pack s operate as slave unit s under the control of a single master VTR73XX Terminal Equipment Controller A single VTR73XX Terminal Equipment Contro...

Страница 2: ...el dependent The VC3xxxX Relay Pack supplies power to the wall VTR73xxA Terminal Equipment Controller The VTR73xxA Controller operates the VC3xxxX Relay Pack s via a simple communication bus A maximum...

Страница 3: ...or is opened any movements detected by the remote PIR sensor or the PIR accessory cover will be ignored Use a Normally Closed contact switching device Contact opened Door opened Contact closed Door cl...

Страница 4: ...ews in mounting holes on each side of the base Fig 4 8 Gently swing back the circuit board on the base and push on it until the tabs lock it 9 1Strip each wire 1 4 inch 10 Insert each wire according t...

Страница 5: ...single VTR73xxA Terminal Equipment Controller From the VTR73xxA Terminal Equipment Controller to the first VC3xxxX Relay Pack o Existing or new field wires o 3 minimum required 14 22 Ga Solid or Stran...

Страница 6: ...conditional to Humidity display is model and configuration dependent Model with RH sensor built in Display function can be enabled with RH display parameter Displayed range is 10 to 90 RH Outdoor air...

Страница 7: ...ertain functions is made with configuration parameter lockout Local Setpoint Adjustment when Stp Func Dual Stp Dual Occupied Setpoints Adjustment Occupied setpoint adjustments Cooling mode Heating mod...

Страница 8: ...t will be strictly for noise comfort issues Auto Speed Fan Mode operation for sequences 2 and 3 is dependent on Auto Fan parameter When Auto Fan is set to AS Default Auto Speed during occupied periods...

Страница 9: ...erminal Equipment Controller reporting to a gateway maximum of 30 Terminal Equipment Controllers per gateway be sure you set the SAME PAN ID value both at the gateway and the Terminal Equipment Contro...

Страница 10: ...tions using a Normally Open NO or Normally Closed NC remote PIR motion sensor Occupancy mode is now set as per applied PIR function and configuration Application information and examples are available...

Страница 11: ...ed Service a backlit flashing Service alarm will be displayed on the Terminal Equipment Controller LCD screen when the input is energized It can be tied in to the AC unit control card which provides a...

Страница 12: ...from 0 to 2 Will enable heat cool operation from the same output 4 0 Pipes can access all the sequences of operation from 0 to 4 Will enable heat cool operation from different output SeqOpera Sequenc...

Страница 13: ...Terminal Equipment Controller unoccupied mode and setpoints become active The factory value or 0 0 hours Setting this parameter to its default value of 0 0 hours disables the unoccupied timer This pre...

Страница 14: ...e permanent ones and saved to EEPROM Permnent permanent Any change of occupied or unoccupied setpoints through the keypad by the user are permanent and saved to EEPROM SptFunc Local setpoint settings...

Страница 15: ...hour under normal control operation It represents the maximum number of cycles that the equipment will turn ON and OFF in one hour Note that a higher C P H will represent a higher accuracy of control...

Страница 16: ...75 lb 0 34 kg PENDING Agency Approvals all models UL UL 873 US and CSA C22 2 No 24 Canada File E27734 with CCN XAPX US and XAPX7 Canada Industry Canada ICES 003 Canada PENDING Agency Approvals all mod...

Отзывы: