Remote Universal input no.1 
configuration 

Default value = 

None

 

(None): 

No function will be associated with the input. Input can be used for remote 

network monitoring. 
 

(COC/NH) Change over dry contact. Normally Heat: 

Used for hot

 

/

 

cold water or 

air change over switching in 2 pipe systems. 

 

 

Contact closed = Cold water or air present 

 

Contact opened = Hot water or air present 

Only used and valid if system is setup as 2 pipes. Parameter ( Pipe No ) set as 2 
pipes. 

 

 

(COC/NC) Change over dry contact. Normally Cool: 

Used for hot

 

/

 

cold water or 

air change over switching in 2 pipe systems. 

 

 

Contact closed = Hot water present 

 

Contact opened = Cold water present 

Only used and valid if system is setup as 2 pipes. Parameter (Pipe No ) set as 2 
pipes. 

 

(COS) Change over analog sensor: 

Used for hot

 

/

 

cold water or air change over 

switching in 2 pipe systems.

 

Only used and valid if system is setup as 2 pipes. Parameter (Pipe No ) set as 2 
pipes.  

 

If water temperature is > 78 °F = Hot water present 

 

If water temperature is < 75 °F = Cold water present 

 

(Filter): 

a backlit flashing 

Filter 

alarm will be displayed on the Terminal Equipment 

Controller LCD screen when the input is energized. It can be tied to a differential 
pressure switch that monitor filters

  

 

Contact opened = No alarm 

 

Contact closed = Alarm displayed 

 

 

(Service): 

a backlit flashing 

Service 

alarm will be displayed on the Terminal 

Equipment Controller LCD screen when the input is energized. It can be tied in to 
the AC unit control card, which provides an alarm in case of malfunction. 

 

Contact opened = No alarm 

 

Contact closed = Alarm displayed 

 

RBI 2 

Remote Binary input no.2 
configuration 
Default value = 

None

 

(None): 

No function will be associated with the input. Input can be used for remote 

network monitoring. 

 

(Filter): 

a backlit flashing 

Filter 

alarm will be displayed on the Terminal Equipment 

Controller LCD screen when the input is energized. It can be tied to a differential 
pressure switch that monitor filters

  

 

Contact opened = No alarm 

 

Contact closed = Alarm displayed 

 

 

(Service): 

a backlit flashing 

Service 

alarm will be displayed on the Terminal 

Equipment Controller LCD screen when the input is energized. It can be tied in to 
the AC unit control card, which provides an alarm in case of malfunction. 

 

Contact opened = No alarm 

 

Contact closed = Alarm displayed 

 

MenuScro

  

Menu scroll 

Default value = 

On = 

Scroll active

 

Removes the scrolling display and only present the room temperature/humidity to 
the user. With this option enabled, no status is given of mode, schedule and 
outdoor temperature. 

 

On = Scroll active

 

 

Off = Scroll not active 

AutoMode

 

Enables 

Auto

 menu for Mode 

button 
Default value = 

On  

Enables Auto function for the mode button

 

For sequences 2, 4 & 5 only  

 

On = Auto active

 (Off-Cool-Heat-Auto) 

 

Off = auto not active 

(Off-Cool-Heat)

 

Содержание VTR73 Series

Страница 1: ...000 Series Line Voltage Switching Transformer Relay Pack s operate as slave unit s under the control of a single master VTR73XX Terminal Equipment Controller A single VTR73XX Terminal Equipment Contro...

Страница 2: ...el dependent The VC3xxxX Relay Pack supplies power to the wall VTR73xxA Terminal Equipment Controller The VTR73xxA Controller operates the VC3xxxX Relay Pack s via a simple communication bus A maximum...

Страница 3: ...or is opened any movements detected by the remote PIR sensor or the PIR accessory cover will be ignored Use a Normally Closed contact switching device Contact opened Door opened Contact closed Door cl...

Страница 4: ...ews in mounting holes on each side of the base Fig 4 8 Gently swing back the circuit board on the base and push on it until the tabs lock it 9 1Strip each wire 1 4 inch 10 Insert each wire according t...

Страница 5: ...single VTR73xxA Terminal Equipment Controller From the VTR73xxA Terminal Equipment Controller to the first VC3xxxX Relay Pack o Existing or new field wires o 3 minimum required 14 22 Ga Solid or Stran...

Страница 6: ...conditional to Humidity display is model and configuration dependent Model with RH sensor built in Display function can be enabled with RH display parameter Displayed range is 10 to 90 RH Outdoor air...

Страница 7: ...ertain functions is made with configuration parameter lockout Local Setpoint Adjustment when Stp Func Dual Stp Dual Occupied Setpoints Adjustment Occupied setpoint adjustments Cooling mode Heating mod...

Страница 8: ...t will be strictly for noise comfort issues Auto Speed Fan Mode operation for sequences 2 and 3 is dependent on Auto Fan parameter When Auto Fan is set to AS Default Auto Speed during occupied periods...

Страница 9: ...erminal Equipment Controller reporting to a gateway maximum of 30 Terminal Equipment Controllers per gateway be sure you set the SAME PAN ID value both at the gateway and the Terminal Equipment Contro...

Страница 10: ...tions using a Normally Open NO or Normally Closed NC remote PIR motion sensor Occupancy mode is now set as per applied PIR function and configuration Application information and examples are available...

Страница 11: ...ed Service a backlit flashing Service alarm will be displayed on the Terminal Equipment Controller LCD screen when the input is energized It can be tied in to the AC unit control card which provides a...

Страница 12: ...from 0 to 2 Will enable heat cool operation from the same output 4 0 Pipes can access all the sequences of operation from 0 to 4 Will enable heat cool operation from different output SeqOpera Sequenc...

Страница 13: ...Terminal Equipment Controller unoccupied mode and setpoints become active The factory value or 0 0 hours Setting this parameter to its default value of 0 0 hours disables the unoccupied timer This pre...

Страница 14: ...e permanent ones and saved to EEPROM Permnent permanent Any change of occupied or unoccupied setpoints through the keypad by the user are permanent and saved to EEPROM SptFunc Local setpoint settings...

Страница 15: ...hour under normal control operation It represents the maximum number of cycles that the equipment will turn ON and OFF in one hour Note that a higher C P H will represent a higher accuracy of control...

Страница 16: ...75 lb 0 34 kg PENDING Agency Approvals all models UL UL 873 US and CSA C22 2 No 24 Canada File E27734 with CCN XAPX US and XAPX7 Canada Industry Canada ICES 003 Canada PENDING Agency Approvals all mod...

Отзывы: