Programming and status display instructions  

 

 

Status display 

 

The VTR73xxA Terminal Equipment Controller features a two-line, eight-character display. There is a low-level backlight 
level that is always active and can only be seen at night. 

 

When left unattended, the Terminal Equipment Controller has an auto scrolling display that shows the actual status of 
the system. There is an option in the configuration menu to lockout the scrolling display and to only present the room 
temperature and conditional outdoor temperature to the user. With this option enabled, no local status is given of mode, 
occupancy and relative humidity. 

 

Each item is scrolled one by one with the back lighting in low level mode. Pressing any key will cause the back light to 
come on to high level. When left unattended for 10 seconds after changes are made, the display will resume automatic 
status display scrolling. 

 

To turn on the back light to high level, press any key on the front panel. The back lit display will return to low level when 
the Terminal Equipment Controller is left unattended for 45 seconds 

 

Sequence of auto-scroll status display: 

 

Room & Humidity 

 

System Mode 

 

Schedule Status 

Outdoor Temperature 

 

Alarms 

x.x °C or °F 

 

Sys mode 

 

Occupied 

 Outdoor 

 Service 

XX % RH 

 

Auto 

 

 

 

x.x °C or°F 

 

 

If humidity display 
enabled 

 

Sys mode  
Cool  

 

Stand-By 
 

 

Network value only

 

 

Filter 
 

RoomTemp 
x.x °C or °F 

 

Sys mode 
heat 

 

Unoccup 
 

 

 

 

Window 

If humidity display is not 
enabled

 

 

Sys mode  
off 

 

Override 
 

  

 Low 

Batt 

 

% RH display is conditional to: 

(Humidity display is model and configuration dependent)

 

 

Model with RH sensor built in 

 

Display function can be enabled with RH display parameter. Displayed range is 10 to 90 % RH

 

 

Outdoor air temperature  

 

Display is only enabled when outdoor air temperature network variable is received.

 

 

Occupancy Status 

 

Occupied, Stand-By, Unoccupied and Override status are displayed on the scrolling display.

 

 

Alarms 

 

If alarms are detected, they will automatically be displayed at the end of the status display scroll.  

 

During an alarm message display, the backlit screen will light up at the same time as the message and shut off 
during the rest of the status display. 

 

Two alarms maximum can appear at any given time. The priority for the alarms is as follows:

 

 

Service 

Indicates that there is a service alarm as per one of the programmable binary input ( BI2 ) 

Filter 

Indicates that the filters are dirty as per one of the programmable binary input ( BI2 ) 

Window 

Indicates that the outside window or door is opened and that the Terminal Equipment Controller has 
cancelled any cooling or heating action ( BI1 ) 

Low Batt 

Indicates that attached wireless switching devices ( Door or window contact ) have a low battery condition. 
Only functional when used with a wireless communication adapter 

 

Three status LED’s

 on the Terminal Equipment Controller cover are used to indicate the status of the fan ( any speed ), a call for 

heat, or a call for cooling. 
 
Fan coil models

 

 

 

When any of the fan speeds are ON,

 

 

the FAN LED will illuminate. 
 

 

When heating & reheat is ON,  
the HEAT LED will illuminate. 
 

 

When cooling is ON, 
the COOL LED will illuminate. 

Fig.11 – Hotel models °C/°F 

 

Fig. 12 Commercial models with Override 

Содержание VTR73 Series

Страница 1: ...000 Series Line Voltage Switching Transformer Relay Pack s operate as slave unit s under the control of a single master VTR73XX Terminal Equipment Controller A single VTR73XX Terminal Equipment Contro...

Страница 2: ...el dependent The VC3xxxX Relay Pack supplies power to the wall VTR73xxA Terminal Equipment Controller The VTR73xxA Controller operates the VC3xxxX Relay Pack s via a simple communication bus A maximum...

Страница 3: ...or is opened any movements detected by the remote PIR sensor or the PIR accessory cover will be ignored Use a Normally Closed contact switching device Contact opened Door opened Contact closed Door cl...

Страница 4: ...ews in mounting holes on each side of the base Fig 4 8 Gently swing back the circuit board on the base and push on it until the tabs lock it 9 1Strip each wire 1 4 inch 10 Insert each wire according t...

Страница 5: ...single VTR73xxA Terminal Equipment Controller From the VTR73xxA Terminal Equipment Controller to the first VC3xxxX Relay Pack o Existing or new field wires o 3 minimum required 14 22 Ga Solid or Stran...

Страница 6: ...conditional to Humidity display is model and configuration dependent Model with RH sensor built in Display function can be enabled with RH display parameter Displayed range is 10 to 90 RH Outdoor air...

Страница 7: ...ertain functions is made with configuration parameter lockout Local Setpoint Adjustment when Stp Func Dual Stp Dual Occupied Setpoints Adjustment Occupied setpoint adjustments Cooling mode Heating mod...

Страница 8: ...t will be strictly for noise comfort issues Auto Speed Fan Mode operation for sequences 2 and 3 is dependent on Auto Fan parameter When Auto Fan is set to AS Default Auto Speed during occupied periods...

Страница 9: ...erminal Equipment Controller reporting to a gateway maximum of 30 Terminal Equipment Controllers per gateway be sure you set the SAME PAN ID value both at the gateway and the Terminal Equipment Contro...

Страница 10: ...tions using a Normally Open NO or Normally Closed NC remote PIR motion sensor Occupancy mode is now set as per applied PIR function and configuration Application information and examples are available...

Страница 11: ...ed Service a backlit flashing Service alarm will be displayed on the Terminal Equipment Controller LCD screen when the input is energized It can be tied in to the AC unit control card which provides a...

Страница 12: ...from 0 to 2 Will enable heat cool operation from the same output 4 0 Pipes can access all the sequences of operation from 0 to 4 Will enable heat cool operation from different output SeqOpera Sequenc...

Страница 13: ...Terminal Equipment Controller unoccupied mode and setpoints become active The factory value or 0 0 hours Setting this parameter to its default value of 0 0 hours disables the unoccupied timer This pre...

Страница 14: ...e permanent ones and saved to EEPROM Permnent permanent Any change of occupied or unoccupied setpoints through the keypad by the user are permanent and saved to EEPROM SptFunc Local setpoint settings...

Страница 15: ...hour under normal control operation It represents the maximum number of cycles that the equipment will turn ON and OFF in one hour Note that a higher C P H will represent a higher accuracy of control...

Страница 16: ...75 lb 0 34 kg PENDING Agency Approvals all models UL UL 873 US and CSA C22 2 No 24 Canada File E27734 with CCN XAPX US and XAPX7 Canada Industry Canada ICES 003 Canada PENDING Agency Approvals all mod...

Отзывы: