9
Configuration parameters
Default value
Significance and adjustments
PswrdSet
Configuration parameters menu
access password
Default value =
0
Range is:
0 to 1000
This parameter sets a protective access password to prevent unauthorized access
to the configuration menu parameters. A default value of “0” will not prompt a
password or lock the access to the configuration menu.
Range is:
0 to 1000
Com Addr
Terminal Equipment Controller
networking address
Default value =
254
Range is:
0 to 254
Conditional parameter to BACnet MS-TP models VTR73xxX5x00B
Conditional parameter to Wireless models VTR73xxX5x00W
•
For BACnet MS-TP models valid range to use is from 1 to 127. Default value of
254 disables BACnet communication for the Terminal Equipment Controller.
•
For wireless models valid range is 0 to 254 with a maximum of 30 Terminal
Equipment Controller per VWG
PAN ID
Personal Area Network
Identification
Default value = 0
Range is:
0 to 1000
Conditional parameter to Wireless models VTR73xxX5x00W
This parameter will only appear when a wireless network adapter is present. If the
Terminal Equipment Controller is installed as a stand-alone unit or with a BACnet
or Echelon adapter, this parameter will not be used or displayed
This parameter (Personal Area Network Identification) is used to link specific
Terminal Equipment Controllers to a single specific Viconics wireless gateway (
VWG ). For every Terminal Equipment Controller reporting to a gateway (
maximum of 30 Terminal Equipment Controllers per gateway ), be sure you set the
SAME
PAN ID value both at the gateway and the Terminal Equipment
Controller(s).
The default value of 0 is
NOT
a valid PAN ID.
The valid range of available PAN ID is from:
-
PAN ID 1 in association with Channel 26 is reserved for remote wireless
switching device configuration only
-
2 to 500 for applications using the VWG or a Jace with the wireless stat
driver
-
501 to 1000 for stand-alone applications where no VWG or Jace with the
wireless stat driver is used. Stand-Alone applications
Channel
Channel selection
Default value = 10
Range is:
10 to 26
Conditional parameter to Wireless models VTR73xxX5x00W
This parameter will only appear when a wireless network adapter is present. If the
Terminal Equipment Controller is installed as a stand-alone unit or with a BACnet
or Echelon adapter, this parameter will not be used or displayed
This parameter (Channel) is used to link specific Terminal Equipment Controllers to
specific Viconics wireless gateway(s) ( VWG ) For every Terminal Equipment
Controller reporting to a gateway ( maximum of 30 Terminal Equipment Controllers
per gateway ), be sure you set the
SAME
channel value both at the gateway and
the Terminal Equipment Controller(s).
Viconics recommends using only the 2 last channels ( 25-2575MHz and 26-
2580MHz )
The default value of 10 is
NOT
a valid channel. The valid range of available
channel is from 11 to 26
PAN ID 1 in association with Channel 26 is reserved for remote wireless switching