Configuration parameters 
Default value

 

Significance and adjustments

 

PswrdSet

 

Configuration parameters menu 
access password 
Default value = 

Range is: 

0 to 1000

 

This parameter sets a protective access password to prevent unauthorized access 
to the configuration menu parameters. A default value of “0” will not prompt a 
password or lock the access to the configuration menu. 
 
Range is:

 

0 to 1000

 

Com Addr

  

Terminal Equipment Controller 
networking address 
Default value = 

254 

Range is: 

0 to 254 

Conditional parameter to BACnet MS-TP models VTR73xxX5x00B 
Conditional parameter to Wireless models VTR73xxX5x00W 

 

 

For BACnet MS-TP models valid range to use is from 1 to 127. Default value of 
254 disables BACnet communication for the Terminal Equipment Controller. 

 

For wireless models valid range is 0 to 254 with a maximum of 30 Terminal 
Equipment Controller per VWG 

PAN ID

 

Personal Area Network 
Identification 
Default value = 0

 

Range is: 

0 to 1000

 

Conditional parameter to Wireless models VTR73xxX5x00W 

This parameter will only appear when a wireless network adapter is present. If the 
Terminal Equipment Controller is installed as a stand-alone unit or with a BACnet 
or Echelon adapter, this parameter will not be used or displayed 
 
This parameter (Personal Area Network Identification) is used to link specific 
Terminal Equipment Controllers to a single specific Viconics wireless gateway ( 
VWG ). For every Terminal Equipment Controller reporting to a gateway ( 
maximum of 30 Terminal Equipment Controllers per gateway ), be sure you set the 

SAME

 PAN ID value both at the gateway and the Terminal Equipment 

Controller(s).  
 

The default value of 0 is 

NOT

 a valid PAN ID.  

The valid range of available PAN ID is from: 

-

 

PAN ID 1 in association with Channel 26 is reserved for remote wireless 
switching device configuration only 

-

 

2 to 500 for applications using the VWG or a Jace with the wireless stat 
driver 

-

 

501 to 1000 for stand-alone applications where no VWG or Jace with the 
wireless stat driver is used. Stand-Alone applications 

Channel

 

Channel selection 
Default value = 10

 

Range is: 

10 to 26

 

Conditional parameter to Wireless models VTR73xxX5x00W 

This parameter will only appear when a wireless network adapter is present. If the 
Terminal Equipment Controller is installed as a stand-alone unit or with a BACnet 
or Echelon adapter, this parameter will not be used or displayed 
 
This parameter (Channel) is used to link specific Terminal Equipment Controllers to 
specific Viconics wireless gateway(s) ( VWG ) For every Terminal Equipment 
Controller reporting to a gateway ( maximum of 30 Terminal Equipment Controllers 
per gateway ), be sure you set the 

SAME

 channel value both at the gateway and 

the Terminal Equipment Controller(s). 
 

Viconics recommends using only the 2 last channels ( 25-2575MHz and 26-
2580MHz ) 

 
The default value of 10 is 

NOT

 a valid channel. The valid range of available 

channel is from 11 to 26 
 
PAN ID 1 in association with Channel 26 is reserved for remote wireless switching 
device configuration only 

Содержание VTR73 Series

Страница 1: ...000 Series Line Voltage Switching Transformer Relay Pack s operate as slave unit s under the control of a single master VTR73XX Terminal Equipment Controller A single VTR73XX Terminal Equipment Contro...

Страница 2: ...el dependent The VC3xxxX Relay Pack supplies power to the wall VTR73xxA Terminal Equipment Controller The VTR73xxA Controller operates the VC3xxxX Relay Pack s via a simple communication bus A maximum...

Страница 3: ...or is opened any movements detected by the remote PIR sensor or the PIR accessory cover will be ignored Use a Normally Closed contact switching device Contact opened Door opened Contact closed Door cl...

Страница 4: ...ews in mounting holes on each side of the base Fig 4 8 Gently swing back the circuit board on the base and push on it until the tabs lock it 9 1Strip each wire 1 4 inch 10 Insert each wire according t...

Страница 5: ...single VTR73xxA Terminal Equipment Controller From the VTR73xxA Terminal Equipment Controller to the first VC3xxxX Relay Pack o Existing or new field wires o 3 minimum required 14 22 Ga Solid or Stran...

Страница 6: ...conditional to Humidity display is model and configuration dependent Model with RH sensor built in Display function can be enabled with RH display parameter Displayed range is 10 to 90 RH Outdoor air...

Страница 7: ...ertain functions is made with configuration parameter lockout Local Setpoint Adjustment when Stp Func Dual Stp Dual Occupied Setpoints Adjustment Occupied setpoint adjustments Cooling mode Heating mod...

Страница 8: ...t will be strictly for noise comfort issues Auto Speed Fan Mode operation for sequences 2 and 3 is dependent on Auto Fan parameter When Auto Fan is set to AS Default Auto Speed during occupied periods...

Страница 9: ...erminal Equipment Controller reporting to a gateway maximum of 30 Terminal Equipment Controllers per gateway be sure you set the SAME PAN ID value both at the gateway and the Terminal Equipment Contro...

Страница 10: ...tions using a Normally Open NO or Normally Closed NC remote PIR motion sensor Occupancy mode is now set as per applied PIR function and configuration Application information and examples are available...

Страница 11: ...ed Service a backlit flashing Service alarm will be displayed on the Terminal Equipment Controller LCD screen when the input is energized It can be tied in to the AC unit control card which provides a...

Страница 12: ...from 0 to 2 Will enable heat cool operation from the same output 4 0 Pipes can access all the sequences of operation from 0 to 4 Will enable heat cool operation from different output SeqOpera Sequenc...

Страница 13: ...Terminal Equipment Controller unoccupied mode and setpoints become active The factory value or 0 0 hours Setting this parameter to its default value of 0 0 hours disables the unoccupied timer This pre...

Страница 14: ...e permanent ones and saved to EEPROM Permnent permanent Any change of occupied or unoccupied setpoints through the keypad by the user are permanent and saved to EEPROM SptFunc Local setpoint settings...

Страница 15: ...hour under normal control operation It represents the maximum number of cycles that the equipment will turn ON and OFF in one hour Note that a higher C P H will represent a higher accuracy of control...

Страница 16: ...75 lb 0 34 kg PENDING Agency Approvals all models UL UL 873 US and CSA C22 2 No 24 Canada File E27734 with CCN XAPX US and XAPX7 Canada Industry Canada ICES 003 Canada PENDING Agency Approvals all mod...

Отзывы: