2

 

Operation overview 

 

 

 

The VC3xxxX Series Line Voltage Switching Transformer Relay Pack(s) operate as slave unit(s) under the control of a single 
master VTR73xxA Terminal Equipment Controller. 
 
Fan operation can be configured and wired for the following: 

o

 

3 Speed configuration using 3 fan relays ( Low – Med - High ) 

o

 

2 Speed configuration using 2 fan relays ( Low - High ) 

o

 

3 Speed configuration with Auto fan speed mode using 3 fan relays ( Low – Med - High ) 

o

 

2 Speed configuration with Auto fan speed mode using 2 fan relays ( Low - High ) 

o

 

Single fan speed configuration.  

 

The VTR7300 Controller can be configured for typical 2 or 4 pipe heating / cooling FCU applications.  
 

2 or 4 pipe only operation can be configured and wired for the following: 

o

 Cooling 

only 

o

 Heating 

only 

o

 

Cooling / Heating with network or local auto changeover 

 

2 or 4 pipe only with electric reheat can be configured and wired for the following: 

o

 Cooling 

only 

o

 Heating 

only 

o

 

Cooling / Heating with network or local auto changeover 

o

 

On-Off electric reheat only  

o

 

Cooling with On-Off or modulating Vdc pulsed electric reheat ( model dependent ) 

o

 

Heating with On-Off or modulating Vdc pulsed electric reheat ( model dependent ) 

o

 

Cooling / Heating with network or local changeover with On-Off or modulating Vdc pulsed electric reheat ( 

model dependent ) 

 

ƒ

 

The VC3xxxX Relay Pack supplies power to the wall VTR73xxA Terminal Equipment Controller. 

ƒ

 

The VTR73xxA Controller operates the VC3xxxX Relay Pack(s) via a simple communication bus. 

ƒ

 

A maximum of 10 VC3xxxX Relay Pack can be used under a single VTR73xxA Terminal Equipment Controller. 

ƒ

 

3 wires minimum are required between the VTR73xxA Controller and 

the first

 VR7300 Relay Pack. 

ƒ

 

The 3 wire functions are as follow: 

o

 

1 Tx / Rx Communication 

o

 

2 Power Hot 7.0 Vdc 4 Watts maximum ( required for the VTR73xxA Controller power ) 

o

 

3 Power common 

ƒ

 

Commands for fan speed and valve operation are issued from the VTR73xxA Terminal Equipment Controller to the 
VC3xxxX Relay Pack(s) 

  

Typical one to one set-up 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Existing or New Field VTR7300 Wires

3 minimum required 14-22 Ga

Solid or Stranded

H

C

High Voltage in cabinet wiring

- Line powered 90 to 277 Vac
- Line switching of fan & valves 90 to 277 Vac
- Isolated heating output for electric reheat

Line Voltage Power

Line Voltage Valves

- 2 pipes or 4 pipes applications
- Isolated line switching for electric reheat

Line Voltage Fan

- Configurable
- Up to 3 speed
   fan control
- Auto fan speed

 

Local Inputs at VTR7300 Controller

Special optional local function(s):

- Remote motion detector(s)

- Window contacts

- Occupancy card holder

Model Dependent

Optional FCU Monitoring Inputs

- Service or Filter alarms

- Supply air sensor

- Return air sensor

- Changeover sensor or contact

Existing or New Communication Field Wires

 - BACnet MS-TP
 - LON TP-FT 10
 - Wireless ( No wires )

Содержание VTR73 Series

Страница 1: ...000 Series Line Voltage Switching Transformer Relay Pack s operate as slave unit s under the control of a single master VTR73XX Terminal Equipment Controller A single VTR73XX Terminal Equipment Contro...

Страница 2: ...el dependent The VC3xxxX Relay Pack supplies power to the wall VTR73xxA Terminal Equipment Controller The VTR73xxA Controller operates the VC3xxxX Relay Pack s via a simple communication bus A maximum...

Страница 3: ...or is opened any movements detected by the remote PIR sensor or the PIR accessory cover will be ignored Use a Normally Closed contact switching device Contact opened Door opened Contact closed Door cl...

Страница 4: ...ews in mounting holes on each side of the base Fig 4 8 Gently swing back the circuit board on the base and push on it until the tabs lock it 9 1Strip each wire 1 4 inch 10 Insert each wire according t...

Страница 5: ...single VTR73xxA Terminal Equipment Controller From the VTR73xxA Terminal Equipment Controller to the first VC3xxxX Relay Pack o Existing or new field wires o 3 minimum required 14 22 Ga Solid or Stran...

Страница 6: ...conditional to Humidity display is model and configuration dependent Model with RH sensor built in Display function can be enabled with RH display parameter Displayed range is 10 to 90 RH Outdoor air...

Страница 7: ...ertain functions is made with configuration parameter lockout Local Setpoint Adjustment when Stp Func Dual Stp Dual Occupied Setpoints Adjustment Occupied setpoint adjustments Cooling mode Heating mod...

Страница 8: ...t will be strictly for noise comfort issues Auto Speed Fan Mode operation for sequences 2 and 3 is dependent on Auto Fan parameter When Auto Fan is set to AS Default Auto Speed during occupied periods...

Страница 9: ...erminal Equipment Controller reporting to a gateway maximum of 30 Terminal Equipment Controllers per gateway be sure you set the SAME PAN ID value both at the gateway and the Terminal Equipment Contro...

Страница 10: ...tions using a Normally Open NO or Normally Closed NC remote PIR motion sensor Occupancy mode is now set as per applied PIR function and configuration Application information and examples are available...

Страница 11: ...ed Service a backlit flashing Service alarm will be displayed on the Terminal Equipment Controller LCD screen when the input is energized It can be tied in to the AC unit control card which provides a...

Страница 12: ...from 0 to 2 Will enable heat cool operation from the same output 4 0 Pipes can access all the sequences of operation from 0 to 4 Will enable heat cool operation from different output SeqOpera Sequenc...

Страница 13: ...Terminal Equipment Controller unoccupied mode and setpoints become active The factory value or 0 0 hours Setting this parameter to its default value of 0 0 hours disables the unoccupied timer This pre...

Страница 14: ...e permanent ones and saved to EEPROM Permnent permanent Any change of occupied or unoccupied setpoints through the keypad by the user are permanent and saved to EEPROM SptFunc Local setpoint settings...

Страница 15: ...hour under normal control operation It represents the maximum number of cycles that the equipment will turn ON and OFF in one hour Note that a higher C P H will represent a higher accuracy of control...

Страница 16: ...75 lb 0 34 kg PENDING Agency Approvals all models UL UL 873 US and CSA C22 2 No 24 Canada File E27734 with CCN XAPX US and XAPX7 Canada Industry Canada ICES 003 Canada PENDING Agency Approvals all mod...

Отзывы: