VTR73xxA Terminal Equipment Controller Installation  

 

 
Remove security screw on the bottom of Terminal Equipment Controller cover.  

 

Open up by pulling on the bottom side of Terminal Equipment Controller. 

 

Remove Assembly and remove wiring terminals from sticker. 

(Fig. 3) 

 

Please note the FCC ID and IC label installed in the cover upon removal 
of cover for the wireless products. 

 

A) 

Location:

 

1. Should 

not be installed on an outside wall. 

2.  Must be installed away from any heat source. 

3.  Should not be installed near an air discharge grill. 

4.  Should not be affected by direct sun radiation. 

5. 

Nothing must restrain vertical air circulation to the Terminal Equipment 

Controller.

 

 

B) 

Installation:

 

1.  Swing open the Terminal Equipment Controller PCB to the left by 

pressing the PCB locking tabs. 

(Fig. 4)

 

2.  Pull out cables 6” out of the wall.  

3.  Wall surface must be flat and clean.  

4.  Insert cable in the central hole of the base.

 

 

5.  Align the base and mark the location of the two mounting holes on the 

wall. Install proper side of base up. 

6.

  Install anchors in the wall.

 

7.  Insert screws in mounting holes on each side of the base. 

(Fig. 4)

 

8.  Gently swing back the circuit board on the base and push on it until the 

tabs lock it. 

9.  1Strip each wire 1/4 inch. 

10.  Insert each wire according to wiring diagram.  

11.  Gently push back into hole excess wring 

(Fig. 5) 

12.  Re-Install wiring terminals in correct location. 

(Fig. 5)

 

13.

 Reinstall the cover (top side first) and gently push back extra wire length 

into the hole in the wall.

 

14.  Install security screw. 

 

 

 

  If replacing an old Terminal Equipment Controller, label the 

wires before removal of the old Terminal Equipment 
Controller. 

 

  Electronic controls are static sensitive devices.  Discharge 

yourself properly before manipulation and installing the 
Terminal Equipment Controller. 

 

  Short circuit or wrong wiring may permanently damage the 

Terminal Equipment Controller or the equipment. 

 
 

 

All VTR73xxA series Terminal Equipment Controllers are to 
be used only as operating controls.  Whenever a control 
failure could lead to personal injury and/or loss of property, it 
becomes the responsibility of the user to add safety devices 
and/or alarm system to protect against such catastrophic 
failures.

 

 
 
 
 
 
 
 
 
 
 
 
 
 

 

Location of PCB retaining tabs 

 
 
 
 

 

 
 
 
 
 
 
 
 

 

 

Re-install terminal blocks 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 

 

Thermostat assembly  

(VTR7350F5000W shown) 

 
 

 

 

Fig.3

Fig.5

Fig.4

Fig.6

Содержание VTR73 Series

Страница 1: ...000 Series Line Voltage Switching Transformer Relay Pack s operate as slave unit s under the control of a single master VTR73XX Terminal Equipment Controller A single VTR73XX Terminal Equipment Contro...

Страница 2: ...el dependent The VC3xxxX Relay Pack supplies power to the wall VTR73xxA Terminal Equipment Controller The VTR73xxA Controller operates the VC3xxxX Relay Pack s via a simple communication bus A maximum...

Страница 3: ...or is opened any movements detected by the remote PIR sensor or the PIR accessory cover will be ignored Use a Normally Closed contact switching device Contact opened Door opened Contact closed Door cl...

Страница 4: ...ews in mounting holes on each side of the base Fig 4 8 Gently swing back the circuit board on the base and push on it until the tabs lock it 9 1Strip each wire 1 4 inch 10 Insert each wire according t...

Страница 5: ...single VTR73xxA Terminal Equipment Controller From the VTR73xxA Terminal Equipment Controller to the first VC3xxxX Relay Pack o Existing or new field wires o 3 minimum required 14 22 Ga Solid or Stran...

Страница 6: ...conditional to Humidity display is model and configuration dependent Model with RH sensor built in Display function can be enabled with RH display parameter Displayed range is 10 to 90 RH Outdoor air...

Страница 7: ...ertain functions is made with configuration parameter lockout Local Setpoint Adjustment when Stp Func Dual Stp Dual Occupied Setpoints Adjustment Occupied setpoint adjustments Cooling mode Heating mod...

Страница 8: ...t will be strictly for noise comfort issues Auto Speed Fan Mode operation for sequences 2 and 3 is dependent on Auto Fan parameter When Auto Fan is set to AS Default Auto Speed during occupied periods...

Страница 9: ...erminal Equipment Controller reporting to a gateway maximum of 30 Terminal Equipment Controllers per gateway be sure you set the SAME PAN ID value both at the gateway and the Terminal Equipment Contro...

Страница 10: ...tions using a Normally Open NO or Normally Closed NC remote PIR motion sensor Occupancy mode is now set as per applied PIR function and configuration Application information and examples are available...

Страница 11: ...ed Service a backlit flashing Service alarm will be displayed on the Terminal Equipment Controller LCD screen when the input is energized It can be tied in to the AC unit control card which provides a...

Страница 12: ...from 0 to 2 Will enable heat cool operation from the same output 4 0 Pipes can access all the sequences of operation from 0 to 4 Will enable heat cool operation from different output SeqOpera Sequenc...

Страница 13: ...Terminal Equipment Controller unoccupied mode and setpoints become active The factory value or 0 0 hours Setting this parameter to its default value of 0 0 hours disables the unoccupied timer This pre...

Страница 14: ...e permanent ones and saved to EEPROM Permnent permanent Any change of occupied or unoccupied setpoints through the keypad by the user are permanent and saved to EEPROM SptFunc Local setpoint settings...

Страница 15: ...hour under normal control operation It represents the maximum number of cycles that the equipment will turn ON and OFF in one hour Note that a higher C P H will represent a higher accuracy of control...

Страница 16: ...75 lb 0 34 kg PENDING Agency Approvals all models UL UL 873 US and CSA C22 2 No 24 Canada File E27734 with CCN XAPX US and XAPX7 Canada Industry Canada ICES 003 Canada PENDING Agency Approvals all mod...

Отзывы: