Vertiv
™
NetSure
™
802 and Vertiv
™
NetSure
™
8200 -48 VDC Power System
System Application Guide
Spec. No: 582140000
SAG582140000
Model Nos: 802
NLDB
, 802
NLEB
, 802
NL
-
B
,
Proprietary and Confidential © 2022 Vertiv Group Corp.
Revision BH, September 28, 2022
8200
NLDB
, 8200
NLEB
and 8200
NL
-
B
Page 34
List C: 24 Position Bullet-Nose Circuit Breaker/Fuse Panel
Features
♦
Provides twenty-four (24) bullet nose device positions.
♦
Accepts a choice of TLS/TPS-type fuseholders, bullet nose-type circuit breakers, or bullet nose-type GMT fuse modules.
♦
The List C Fuse/Circuit Breaker Panel is equipped with one (1) shunt for all distribution positions for controller load
current measurements.
♦
Bullet Nose-Type Circuit Breakers and Bullet Nose-Type Fuseholders e/w TLS/TPS Fuses
Bullet Nose-Type 10-Position GMT Fuse Module for List C
Restrictions
Each List 16 / List 116, List 17 / List 117, List 18 / List 118, List 22 / List 122, distribution only bay can be equipped with only one
(1) List C panel.
The List C Circuit Breaker/Fuse Panel requires distribution position #12 in the Bus #1 Distribution Panel.
Current monitoring for the List C Fuse/Circuit Breaker Panel is for the complete panel. Circuit breakers and/or fuses are not
individually monitored.
When installed, the distribution only bay can be loaded with up to (47) 218 circuit breakers or (23) TPL fuses and (24) bullet
nose circuit breakers or TLS/TPS fuses.
The List C Circuit Breaker/Fuse Panel is rated for a maximum continuous load of 500 amps.
The total load combination of List C and Distribution Panel #1 cannot exceed 1500A.
Ordering Notes
1)
Order as 5821400000C.
2)
Also order distribution fuses, circuit breakers, and/or bullet nose-type 10-position GMT fuse modules as required per
in the
ACCESSORY DESCRIPTIONS
section.
Optional List C
Bullet Nose Device Panel
Front door removed in
illustration for clarity.