Power/Distribution Bay and Distribution Only Bay Load Distribution Wire Sizes and Lugs
Features
♦
Load distribution leads are connected as described in the sections titled
Distribution Devices and Load Lug Locations -
Distribution Device and Load Lug Locations – Distribution Only Bays
under "Accessory
Descriptions". For lug mounting hole size and spacing dimensions, refer to the illustrations in these sections.
Restrictions
All lugs for customer connections must be ordered separately.
Ordering Notes
1)
The type of distribution device determines the load lug hole size and spacing requirements. The rating of the
distribution device determines the wire size requirements. For wire size and lug selection; refer to Tables
(Load
Side). Load return leads for power/distribution bays are terminated either inside the bay if equipped with the optional
internal ground busbar, or outside the bay if equipped with the optional external ground busbar mounted on top of the
bay. Load return leads for distribution only bays are terminated outside the bay to customer provided return busbars.
2)
Lugs should be crimped per lug manufacturer’s specifications.