5)
Order DC output cable lugs as required per
Power Only Bay DC Output Cable Sizes and Lugs
ACCESSORY
DESCRIPTIONS
section.
6)
Order AC input lugs as required per
Power Only Bay AC Input, Ten (10) Rectifier Feed Wire Sizes, Branch Circuit
in the
ACCESSORY DESCRIPTIONS
section.
7)
Order external top-mount battery input busbar assembly, busbar shield kit, external top-mount ground (load return)
busbar assembly, and/or load return lug extension busbar assembly as required per the appropriate sections located
under
8)
If secondary bays are placed on both sides of the primary bay, a different length Network cable is required that connects
a secondary bay on one side with a secondary bay on the other side. Order per
Replacement/Additional Network Cables
9)
Side cover panels are provided with primary bays. These cover panels are used with secondary bays when bays are
placed next to each other. In installations where a secondary bay is placed by itself, order (1) of each of the following side
cover panels per exposed side: P/N 514482 and P/N 514484.
List 16 and 116: Distribution Only Bay (Cable Only Bay) Left or Right
Features
♦
For use with cable to overhead bus external term bars (left or right).
♦
Provides common equipment for one (1) distribution only bay rated for up to 6000 amperes.
♦
Mounted in a 7'0"H x 31.375"W x 30"D seismic rated (Zone 4) box framework.
♦
Provides forty-eight (48) distribution device mounting positions.
♦
Provides four (4) buses of distribution. When used with the MCA, each bus contains a monitoring circuit card; which can
be set for no group designation, Group A designation, or Group B designation.
♦
Includes a router or CAN interface assembly for bay communication to the controller/monitor in the primary power bay.
♦
Network bay interconnect cable provided (P/N 514643 and P/N 514644).
Restrictions
The system must consist of one (1) primary power/distribution bay or primary power only bay and may consist of up to seven
(7) additional bays. These additional bays may be a combination of secondary power/distribution bays, secondary power only
bays, and/or distribution only bays (maximum of 4 distribution only bays per system).
Requires external main battery termination bars.
Ordering Notes
1)
Order distribution fuse and/or circuit breaker devices as required per
in the
ACCESSORY
DESCRIPTIONS
section.
2)
Order bay grounding lugs as required per
Distribution Only Bay Frame Grounding Wire Sizes and Lugs Selection
ACCESSORY DESCRIPTIONS
section.
3)
Order load distribution lugs as required per
Power/Distribution Bay and Distribution Only Bay Load Distribution Wire
in the
ACCESSORY DESCRIPTIONS
section.
4)
Order DC input cable lugs as required per
Distribution Only Bay DC Input Cable Sizes and Lugs Selection
in the
ACCESSORY DESCRIPTIONS
section.
5)
Order one (1) “Twenty-Four (24) Position Bullet-Nose Circuit Breaker/Fuse Panel” per distribution bay as required per
6)
If a different length Network cable is required, order per
Replacement/Additional Network Cables
7)
Side cover panels are factory installed on one side of the bay. In installations where a distribution only bay is placed by
itself, order (2) P/N 528633 side cover panels for the other side.
List 17 and 117: 2nd Internal Bus Distribution Only Bay – Expansion to the Right or Left
Features
♦
Provides common equipment for one (1) “distribution only” bay rated for up to 6000 amperes.
♦
Mounted in a 7'0"H x 31.375"W x 30"D seismic rated (Zone 4) box framework.
♦
Provides forty-eight (48) distribution device mounting positions.
♦
Provides four (4) buses of distribution. When used with the MCA, each bus contains a monitoring circuit card; which can
be set for no group designation, Group A designation, or Group B designation.