9)
Order AC input lugs as required per
Power/Distribution Bay AC Input, Ten (10) Rectifier Feeds Wire Sizes, Branch Circuit
in the
ACCESSORY DESCRIPTIONS
section.
10)
Order internal ground busbar assembly, external top-mount battery input busbar assembly, busbar shield kit, external
top-mount ground (load return) busbar assembly, and/or load return lug extension busbar assembly as required per the
appropriate sections located under
11)
If the system is to be connected to an existing system with an MCA, refer to List 64, 65, 66, and 67.
List 2 and 102: Primary Power/Distribution Bay (Common Equipment)
Features
♦
Provides common equipment for one (1) “power and distribution” bay rated for up to 2400 amperes.
♦
Mounted in a 7'0"H x 24"W x 30"D Box Framework.
♦
Provides ten (10) rectifier mounting positions.
♦
Provides forty-eight (48) distribution device mounting positions.
♦
Provides two (2) buses of distribution. When used with the MCA, each bus contains a monitoring circuit card; which can
be set for no group designation, Group A designation, or Group B designation.
♦
Configured for a 4000 A internal bus or external main battery termination bars.
♦
List 2: Equipped with an MCA Assembly and provides mounting for optional LMS Main CPU circuit card. Provides a
seven-slot card cage for mounting MCA customer alarm relay circuit cards, MCA I/O circuit cards, and/or optional LMS
I/O circuit cards. Two (2) MCA customer alarm relay circuit cards provided.
♦
List 102: Equipped with an NCU controller and front panel touch screen PC for local access to the NCU webpages.
Includes an IB4 board which provides a Network connection point for NCU remote access. Includes the IB2 NCU
interface board (provides eight (8) programmable form C- relay outputs, eight (8) programmable binary inputs, and two
(2) temperature inputs). Includes the EIB NCU extended interface board (provides five (5) programmable form-C relay
outputs, two (2) temperature inputs, three (3) shunt inputs. and eight (8) battery midpoint inputs).
♦
Expandable either left or right.
♦
Surge suppression optional.
Restrictions
The system must consist of one (1) primary power/distribution bay or primary power only bay and may consist of up to seven
(7) additional bays. These additional bays may be a combination of secondary power/distribution bays, secondary power only
bays, and/or distribution only bays (maximum of 4 distribution only bays per system).
Requires
(480 VAC Input),
PDSC (AC Input 'Power Distribution Service Cabinet').
Ordering Notes
1)
(208 VAC Input).
2)
Order Bolt-On PDSC (AC Input 'Power Distribution Service Cabinet') per
(208 VAC Input).
3)
Order rectifiers as required per
(480 VAC Input) or
(208 VAC Input).
4)
Order distribution fuse and/or circuit breaker devices as required per
in the
ACCESSORY
DESCRIPTIONS
section.
5)
List 2: Order additional MCA customer alarm relay circuit card(s) as required per
cards per
. Order optional LMS Monitor and LMS options as required per
Battery Charge Temperature Compensation Probe as required per
Battery Charge Temperature Compensation Probe for
ACCESSORY DESCRIPTIONS
section.
6)
List 102: Order temperature probes as required per
in the
ACCESSORY DESCRIPTIONS
section.
7)
Order bay grounding lugs as required per
Power/Distribution Bay Frame Grounding Wire Sizes and Lugs
in the
ACCESSORY DESCRIPTIONS
section.
8)
Order load distribution lugs as required per
Power/Distribution Bay and Distribution Only Bay Load Distribution Wire
in the
ACCESSORY DESCRIPTIONS
section.
9)
Order battery cable lugs as required per
Power/Distribution Bay Battery Cable Sizes and Lugs
in the
ACCESSORY
DESCRIPTIONS
section.