Vertiv
™
NetSure
™
802 and Vertiv
™
NetSure
™
8200 -48 VDC Power System
System Application Guide
Spec. No: 582140000
SAG582140000
Model Nos: 802
NLDB
, 802
NLEB
, 802
NL
-
B
,
Proprietary and Confidential © 2022 Vertiv Group Corp.
Revision BH, September 28, 2022
8200
NLDB
, 8200
NLEB
and 8200
NL
-
B
Page 126
Item
Description
Input Power
Input voltage range: 19 VDC to 60 VDC.
Maximum input non-destructive voltage: 75 VDC.
Input Signals
Ten (10) Load Bus Voltage
Valid measurement voltage range: 0 VDC to 60 VDC.
Ten (10) Load Fuse Alarm
Bus- base of 0 VDC, >10 VDC alarm, <10 VDC normal.
Ten (10) Analog Inputs
Each can be set to accept one (1) of the following inputs:
•
10 mV DC to 50 mV DC Load Shunt (only load shunts
are supported at this time)
•
0 mA to 20 mA General-Purpose Transducer
•
0 VDC to 10 VDC General-Purpose Transducer
•
1 uA/K Temperature Sensor
Output Signals
+5 VDC Output for External Hall Devices
Communication
One (1) RS-485 Port
(factory use only)
RS-485 isolated asynchronous port.
Baud rate: 9600/19200 bps, set by hardware.
Data format: N, 8, 1.
One (1) CAN Bus Port
CAN baud rate: 125 Kbps.
Environmental
Ambient Temperature
Normal: -10
°
C to +65
°
C.
Non Destructive: -40
°
C to +75
°
C.
Humidity
Less than 90% without condensation.
Environment
Atmosphere free of dust, corrosive or explosive vapors, oily
fumes, moisture, condensation, metallic particulates, and
salinity.
Altitude
Under 3000 meters.
Cooling Mode
Air cooling without fan.
EMC
Complies with standards: EN 55022, EN 61000-4-6, EN 61000-4-2, EN 61000-4-4,
EN 61000-4-5, and EN 61000-4-29.
Safety
Complies with standards: EN60950, UL60950, GR-63, and GR-1089.
Safety certifications: CE, UL.
Meets the requirements of NEBS level 3.
Table 22
SM-DUE General Technical Specifications