Vertiv
™
NetSure
™
802 and Vertiv
™
NetSure
™
8200 -48 VDC Power System
System Application Guide
Spec. No: 582140000
SAG582140000
Model Nos: 802
NLDB
, 802
NLEB
, 802
NL
-
B
,
Proprietary and Confidential © 2022 Vertiv Group Corp.
Revision BH, September 28, 2022
8200
NLDB
, 8200
NLEB
and 8200
NL
-
B
Page 28
♦
Includes a router or CAN interface assembly for bay communication to the controller/monitor in the primary power bay.
♦
Network bay interconnect cable provided (P/N 514643).
Restrictions
The system must consist of one (1) primary power/distribution bay or primary power only bay and may consist of up to seven
(7) additional bays. These additional bays may be a combination of secondary power/distribution bays, secondary power only
bays, and/or distribution only bays (maximum of 4 distribution only bays per system).
Must be installed to the left or right of a distribution only bay.
Cannot be installed ‘in-between’ power/distribution bays.
Ordering Notes
1)
Order distribution fuse and/or circuit breaker devices as required per
in the
ACCESSORY
DESCRIPTIONS
section.
2)
Order bay grounding lugs as required per
Distribution Only Bay Frame Grounding Wire Sizes and Lugs Selection
ACCESSORY DESCRIPTIONS
section.
3)
Order load distribution lugs as required per
Power/Distribution Bay and Distribution Only Bay Load Distribution Wire
in the
ACCESSORY DESCRIPTIONS
section.
4)
Order one (1) “Twenty-Four (24) Position Bullet-Nose Circuit Breaker/Fuse Panel” per distribution bay as required per
5)
Side cover panels are provided with the 1st distribution only bay. These cover panels are moved to the last distribution
only bay in the bay line-up.
List 18 and 118: 1st Internal Bus Distribution Only Bay – Expansion to the Right
Features
♦
Provides common equipment for one (1) “distribution only” bay rated for up to 6000 amperes.
♦
Mounted in a 7'0"H x 31.375"W x 30"D seismic rated (Zone 4) box framework.
♦
Provides forty-eight (48) distribution device mounting positions.
♦
Provides four (4) buses of distribution. When used with the MCA, each bus contains a monitoring circuit card; which can
be set for no group designation, Group A designation, or Group B designation.
♦
Includes a router or CAN interface assembly for bay communication to the controller/monitor in the primary power bay.
♦
Network bay interconnect cable provided (P/N 514642).
Restrictions
The system must consist of one (1) primary power/distribution bay or primary power only bay and may consist of up to seven
(7) additional bays. These additional bays may be a combination of secondary power/distribution bays, secondary power only
bays, and/or distribution only bays (maximum of 4 distribution only bays per system).
Must be installed to the right of the power/distribution bay line-up (as viewed facing the front).
Cannot be installed ‘in-between’ power/distribution bays, only at the end of the power/distribution bay line-up.
Ordering Notes
1)
Order distribution fuse and/or circuit breaker devices as required per
in the
ACCESSORY
DESCRIPTIONS
section.
2)
Order bay grounding lugs as required per
Distribution Only Bay Frame Grounding Wire Sizes and Lugs Selection
ACCESSORY DESCRIPTIONS
section.
3)
Order load distribution lugs as required per
Power/Distribution Bay and Distribution Only Bay Load Distribution Wire
in the
ACCESSORY DESCRIPTIONS
section.
4)
Order one (1) “Twenty-Four (24) Position Bullet-Nose Circuit Breaker/Fuse Panel” per distribution bay as required per
5)
Side cover panels are provided with the 1st distribution only bay. These cover panels are moved to the last distribution
only bay in the bay line-up.