Restrictions
The system must consist of one (1) primary power/distribution bay or primary power only bay and may consist of up to seven
(7) additional bays. These additional bays may be a combination of secondary power/distribution bays, secondary power only
bays, and/or distribution only bays (maximum of 4 distribution only bays per system).
Requires external main battery termination bars.
Ordering Notes
1)
(208 VAC Input).
2)
If List A specified, bay will include ten (10) P/N 256933200 30 A circuit breakers.
3)
If List B specified, bay will include ten (10) P/N 256937200 60 A circuit breakers.
4)
Order rectifiers as required per
(480 VAC Input) or
(208 VAC Input).
5)
List 13: Order additional MCA customer alarm relay circuit card(s) as required per
, and optional MCA I/O circuit
cards per
. Order optional LMS Expansion CPU circuit card and LMS options as required per
, and
SAG586505000. Also order additional LMS Network cables as required per
Replacement/Additional LMS Network
6)
Order bay grounding lugs as required per
Power Only Bay Frame Grounding Wire Sizes and Lugs
ACCESSORY
DESCRIPTIONS
section.
7)
Order DC output cable lugs as required per
Power Only Bay DC Output Cable Sizes and Lugs
ACCESSORY
DESCRIPTIONS
section.
8)
Order AC input lugs as required per
Power Only Bay AC Input, Five (5) Rectifier Feeds Wire Sizes, Branch Circuit
in the
ACCESSORY DESCRIPTIONS
section.
9)
Order external top-mount battery input busbar assembly, busbar shield kit, external top-mount ground (load return)
busbar assembly, and/or load return lug extension busbar assembly as required per the appropriate sections located
under
10)
If secondary bays are placed on both sides of the primary bay, a different length Network cable is required that connects
a secondary bay on one side with a secondary bay on the other side. Order per
Replacement/Additional Network Cables
11)
Side cover panels are provided with primary bays. These cover panels are used with secondary bays when bays are
placed next to each other. In installations where a secondary bay is placed by itself, order (1) of each of the following side
cover panels per exposed side: P/N 514482 and P/N 514484.
List 14 and 114: Secondary Power Only Bay, Two (2) AC Feeds (Common Equipment)
Features
♦
Provides common equipment for one (1) power only bay rated for up to 2200 amperes.
♦
Mounted in a 7’0”H x 24"W x 30"D box framework.
♦
Provides ten (10) rectifier mounting positions.
♦
Provides AC input circuit breakers rated for 22kA interrupting capacity for each rectifier position. Circuit breakers are
pad-lockable.
♦
Includes a router or CAN interface assembly for bay communication to the controller/monitor in the primary power bay.
♦
List 14: Provides mounting for optional LMS Expansion CPU circuit card. Provides a seven-slot card cage for mounting
MCA customer alarm relay circuit cards, MCA I/O circuit cards, and/or optional LMS I/O circuit cards.
♦
List 114: Includes the SM-DUE. Refer to “
♦
Network bay interconnect cables provided (Qty. 1 P/N 514643, Qty. 1 P/N 509900).
♦
Expandable either left or right, cable connected.
♦
Surge suppression optional.
Restrictions
The system must consist of one (1) primary power/distribution bay or primary power only bay and may consist of up to seven
(7) additional bays. These additional bays may be a combination of secondary power/distribution bays, secondary power only
bays, and/or distribution only bays (maximum of 4 distribution only bays per system).
Requires external main battery termination bars.
Ordering Notes
1)
(208 VAC Input).