Please note that List 35, List 36, List 37, and List 38 Transient Voltage Surge Protector (TVSS) units designed to be used with
solidly grounded electrical systems and are not compatible with High Resistance Grounding for electrical systems. On a HRG
system, L-G voltage rises to the rated line voltage during a bolted ground fault. At this voltage the TVSS which is expecting
to see a Line to Neutral Voltage would read a Line to Line Voltage across it, which would stress the TVSS and eventually
cause the TVSS to fail.
Ordering Notes
1)
Order if additional surge suppression is required.
2)
A wire harness is factory connected to Form-C relay contacts located on each surge suppression assembly for remote
monitoring. Connect the wire harness to the controller’s binary inputs. The controller then provides alarm display
messages and an audible alarm when a surge suppression assembly activates.
List 50: Optional LMS Main CPU Circuit Card (Primary Power/Distribution and Primary Power Only Bays)
Features
♦
Provides the LMS Monitoring System.
♦
Refer to SAG586505000 for further information.
Restrictions
For use with List 1, 2, 3, 4, and 5 only.
The LMS Monitoring System Main CPU circuit card is mounted in the primary power/distribution and primary power only
bays.
Ordering Notes
1)
Order the optional LMS Monitor if increased monitoring capabilities are required. Order the LMS Main CPU circuit card
(List 50) for the primary power/distribution and primary power only bays. Order the LMS Expansion CPU circuit card
(List 63) for secondary power/distribution and secondary power only bays that are to be equipped with LMS I/O circuit
cards.
2)
Order additional LMS Network cables as required per
Replacement/Additional LMS Network Cables
. Note that LMS
Network cables are factory provided with Lists 11, 12, 13, 14, and 15.
3)
This List option only provides the LMS CPU circuit card for the primary power/distribution and primary power only bays,
additional LMS options must be ordered separately per SAG586505000.
List 63: Optional LMS Expansion CPU Circuit Card (Secondary Power/Distribution and Secondary Power Only Bays)
Features
♦
Allows LMS I/O cards to be installed in secondary power/distribution and secondary power only bays.
Restrictions
For use with List 11, 12, 13, 14, and 15 only.
The LMS Monitoring System Expansion CPU circuit cards are mounted in secondary power/distribution and secondary power
only bays (required only if LMS I/O circuit cards are to be installed in the same bay).
Ordering Notes
1)
Order the LMS Expansion CPU circuit card for secondary power/distribution and secondary power only bays that are to
be equipped with LMS I/O circuit cards.
List 70: Additional MCA Six (6) Output Form-C Relay Circuit Card
Features
♦
Provides six relays each with one set of Form-C relay contacts.
♦
These relays are used for alarm applications and can be programmed by the user.
♦
Refer to the "
" section of this document for further information.
♦
Plugs into any slot in 7-position card cage in primary and secondary power/distribution and secondary power only Bays.
♦
User maps relay closure to any or multiple programmable alarm functions.
Restrictions
For use with List 1, 2, 3, 4, 5, 11, 12, 13, 14, or 15 only.
Relay contacts rated for 2A at 30 volts DC.