The reading displayed for the NPS system parameter “Total Auxiliary Load” is derived from the
sum of all analog input readings of CAN I/O cards configured for “Auxiliary” mode operation
5.
OPTIONAL LMS MONITORING SYSTEM
Refer to SAG586505000.
6.
NCU CONTROLLER (IF FURNISHED)
6.1
Specifications
6.1.1
For NCU controller specifications, refer to the NCU controller instructions (UM1M830BNA).
6.2
Configuration
6.2.1
For NCU controller factory settings, refer to the NCU controller configuration drawing (C-drawing).
6.3
IB2 and EIB (NCU Interface Board) Ratings
6.3.1
Digital Input Ratings
(A)
Maximum Voltage Rating: 60V DC.
(B)
Active High: > 19V DC.
(C)
Active Low: < 1V DC.
6.3.2
Relay Ratings
(A)
Steady State: 0.5 A @ 60 VDC; 1 A @ 30 VDC.
(B)
Peak: 3 A @ 30 VDC.
6.4
SM-DUE Ratings