Vertiv
™
NetSure
™
802 and Vertiv
™
NetSure
™
8200 -48 VDC Power System
System Application Guide
Spec. No: 582140000
SAG582140000
Model Nos: 802
NLDB
, 802
NLEB
, 802
NL
-
B
,
Proprietary and Confidential © 2022 Vertiv Group Corp.
Revision BH, September 28, 2022
8200
NLDB
, 8200
NLEB
and 8200
NL
-
B
Page 54
Bullet Nose-Type Circuit Breakers and Bullet Nose-Type Fuseholders e/w TLS/TPS Fuses – Distribution Only Bays
Features
♦
Installs in the optional
Fuse/Circuit Breaker Panel.
♦
Load lugs are connected to busbars provided on the List C Fuse/Circuit Breaker Panel. These busbars provide 1/4-20
threaded holes on 5/8" centers for installation of customer provided two-hole lugs. Load return leads are terminated
outside the bay to customer provided return busbars.
♦
Each circuit breaker (as listed in
) plugs into one, two, or three mounting position(s).
♦
A single fuseholder provides for installation of a 3 to 100 ampere Bussmann TPS-type or Littelfuse TLS-type fuse (as
listed in
). This fuseholder plugs into a single mounting position. This fuseholder provides a GMT-A alarm type
fuse, which operates open to provide an alarm indication if the associated distribution fuse opens.
Restrictions
Load should not exceed 80% of device rating.
Caution: An overcurrent protective device with a rating of 150 amperes or greater SHALL HAVE an empty mounting
position between it and any other overcurrent protective device within the List C Fuse/Circuit Breaker Panel.
Maximum size of wire to be connected to a single lug position is 2 AWG.
Maximum lug width is 0.610.
Customer must provide lug mounting bolts and additional hardware.
Bolt length: 3/4”.
Load return leads are terminated outside the bay to customer provided return busbars.
Ordering Notes
1)
Order circuit breakers per
and
2)
Order fuses per Table 5. For each fuse ordered, also order one (1) P/N 117201 bullet nose type fuseholder.
3)
See Table 10 for recommended load distribution wire sizes and lugs.