4 EQUIPMENT INSPECTION AND HANDLING
WARNING! Risk of top-heavy unit falling over. Improper handling can cause equipment damage, injury, or
death. Read all of the following instructions and verify that all lifting and moving equipment is rated for the
weight of the unit before attempting to move, lift, remove packaging from, or prepare the unit for installation.
CAUTION: Risk of contact with sharp edges, splinters, and exposed fasteners. Can cause injury. Only
properly trained and qualified personnel wearing appropriate, OSHA approved PPE should attempt to move,
lift, remove packaging from, or prepare the unit for installation.
NOTICE
Risk of passageway interference. Can cause unit and/or structure damage. The unit may be too large to fit
through a passageway while on or off the skid. Measure the unit and passageway dimensions, and refer to the
installation plans prior to moving the unit to verify clearances.
NOTICE
Risk of damage from forklift. Can cause unit damage. Keep tines of the forklift level and at a height suitable to
fit below the skid and/or unit to prevent exterior and/or underside damage.
NOTICE
Risk of improper storage. Keep the unit upright, indoors, and protected from dampness, freezing temperatures,
and contact damage.
Upon arrival of the unit and before unpacking:
•
Verify that the labeled equipment matches the bill of lading.
•
Carefully inspect all items for visible or concealed damage.
•
Report damage immediately to the carrier and file a damage claim with a copy sent to Vertiv or to your sales
representative
Equipment Recommended for Handling the Unit:
•
Forklift
•
Pallet jack
•
Piano jacks
4.1 Storing Before Installation
If storing the unit for long periods before installation:
•
Keep the packaging on the unit and allow proper clearance around the unit to perform periodic inspections and
maintenance.
•
Inspect the unit periodically for condensation inside the unit or other signs of other effects of the storage
environment.
•
Rotate the fans and motor shaft by hand periodically for several revolutions. Look for signs of lubrication
problem or obstructions. Failure to regularly rotate fans on a stored unit will result in premature fan failure. This
type of failure is not covered by warranty.
4 Equipment Inspection and Handling
15
Содержание Liebert XDU 060
Страница 1: ...Liebert XDU Liquid to Air Heat Exchanger for Chip Cooling Installer User Guide 600 mm Wide ...
Страница 10: ...Vertiv XDU Liquid to Air Heat Exchanger for Chip Cooling 6 This page intentionally left blank ...
Страница 14: ...Vertiv XDU Liquid to Air Heat Exchanger for Chip Cooling 10 This page intentionally left blank ...
Страница 18: ...Vertiv XDU Liquid to Air Heat Exchanger for Chip Cooling 14 This page intentionally left blank ...
Страница 38: ...Vertiv XDU Liquid to Air Heat Exchanger for Chip Cooling 34 ...
Страница 42: ...Vertiv XDU Liquid to Air Heat Exchanger for Chip Cooling 38 This page intentionally left blank ...
Страница 52: ...Vertiv XDU Liquid to Air Heat Exchanger for Chip Cooling 48 This page intentionally left blank ...
Страница 56: ...Vertiv XDU Liquid to Air Heat Exchanger for Chip Cooling 52 This page intentionally left blank ...
Страница 58: ...Vertiv XDU Liquid to Air Heat Exchanger for Chip Cooling 54 This page intentionally left blank ...
Страница 59: ...Appendix B Performance Curves Figure B 1 Liebert XDU Performance Test Results 45 C 113 F LFT 55 ...
Страница 62: ...Vertiv XDU Liquid to Air Heat Exchanger for Chip Cooling 58 This page intentionally left blank ...
Страница 64: ...Vertiv XDU Liquid to Air Heat Exchanger for Chip Cooling 60 This page intentionally left blank ...
Страница 74: ...Vertiv XDU Liquid to Air Heat Exchanger for Chip Cooling ...