9 TROUBLESHOOTING
below lists possible issues, probable causes, and corrective steps.
Symptom
Possible Cause
Check or Remedy
Pump will not energize
No main power
Check L1, L2, and L3 for rated voltage.
Loose electrical connections
Tighten connections.
Overloads tripped
Allow pump to cool. Check amp draw.
Blown fuse
Check fuses to pump(s).
Incorrect phase wiring
Check wiring phase.
Pump will not start or run
Flow meter not functioning
Check for defective flow meter or miswiring.
VFD error
Check alarm history on unit for PUMP INVRTR FAIL..
No enable signal
Check P1 and P2 relay closure and connections.
No control signal
Check connections at T41 and T42 of VFD.
Pump noisy
Air in the system
Purge air from the high point vent on the top of the unit.
Cavitation due to vapor in pump
Check for adequate charge in system, see
Worn motor bearings
Replace pump.
Pump is rotating in reverse
Check wiring phase.
Pump suddenly stops
Loss of power
When power is restored, the XDU™ Liquid to Air Heat Exchanger for
Chip Cooling automatically restarts.
Clogged strainer/or impeller
Clean out debris.
Pipe rattle
Loose pipe connections
Check pipe connections.
Leaving water temperature high
Low fluid flow
Check alarm history for flow related alarms.
Clean strainer.
Check pressure drop of hose set and connected load.
Check flow meter.
Low air flow
Check alarm history for fan related alarms.
Check for dirt and debris on coil.
Room temperature too high
Reduce room temperature.
Evaporator Fans will not modulate from
100%
Fan control not properly set
Refer to the fan settings descriptions in the
Liebert® iCOM™
Installer/User Guide
available at www.Vertiv.com.
Contact Vertiv Technical Support.
Unit fans fail to start
Fan is faulty
Confirm rear door switches are made.
Contact Vertiv Technical Support.
Top or Bottom Fan Failure Alarm
Confirm line voltage is present at the fan.
Contact Vertiv Technical Support.
Table 9.1 Unit Diagnostics
9 Troubleshooting
39
Содержание Liebert XDU 060
Страница 1: ...Liebert XDU Liquid to Air Heat Exchanger for Chip Cooling Installer User Guide 600 mm Wide ...
Страница 10: ...Vertiv XDU Liquid to Air Heat Exchanger for Chip Cooling 6 This page intentionally left blank ...
Страница 14: ...Vertiv XDU Liquid to Air Heat Exchanger for Chip Cooling 10 This page intentionally left blank ...
Страница 18: ...Vertiv XDU Liquid to Air Heat Exchanger for Chip Cooling 14 This page intentionally left blank ...
Страница 38: ...Vertiv XDU Liquid to Air Heat Exchanger for Chip Cooling 34 ...
Страница 42: ...Vertiv XDU Liquid to Air Heat Exchanger for Chip Cooling 38 This page intentionally left blank ...
Страница 52: ...Vertiv XDU Liquid to Air Heat Exchanger for Chip Cooling 48 This page intentionally left blank ...
Страница 56: ...Vertiv XDU Liquid to Air Heat Exchanger for Chip Cooling 52 This page intentionally left blank ...
Страница 58: ...Vertiv XDU Liquid to Air Heat Exchanger for Chip Cooling 54 This page intentionally left blank ...
Страница 59: ...Appendix B Performance Curves Figure B 1 Liebert XDU Performance Test Results 45 C 113 F LFT 55 ...
Страница 62: ...Vertiv XDU Liquid to Air Heat Exchanger for Chip Cooling 58 This page intentionally left blank ...
Страница 64: ...Vertiv XDU Liquid to Air Heat Exchanger for Chip Cooling 60 This page intentionally left blank ...
Страница 74: ...Vertiv XDU Liquid to Air Heat Exchanger for Chip Cooling ...