Symptom
Possible Cause
Check or Remedy
Local display is not operational, but unit
operates
Local display cable disconnected
Connect cable.
Local display cable damaged
Replace cable.
Local display configuration lost
Contact Vertiv Technical Support.
Local display is not operational, and unit
does not operate
Unit electrical supply is Off
Restore electrical supply.
Unit main switch is Off
Switch On the unit.
Control board supply issue
Contact Vertiv Technical Support.
Control board issue
Contact Vertiv Technical Support.
Main 24 VAC fuse trips
Shorts or loose connections
Check the wiring connections of the 24 VAC circuit.
Faulty circuit board
Replace the circuit board.
XDU™ Liquid to Air Heat Exchanger for Chip
Cooling not making capacity
Air in the system
Check for adequate charge in system, see
page 30. Purge air from the high-point vent on the top of the unit
Entering air temperature too high
Reduce entering air temperature.
Table 9.1 Unit Diagnostics (continued)
Vertiv | XDU™ Liquid to Air Heat Exchanger for Chip Cooling
40
Содержание Liebert XDU 060
Страница 1: ...Liebert XDU Liquid to Air Heat Exchanger for Chip Cooling Installer User Guide 600 mm Wide ...
Страница 10: ...Vertiv XDU Liquid to Air Heat Exchanger for Chip Cooling 6 This page intentionally left blank ...
Страница 14: ...Vertiv XDU Liquid to Air Heat Exchanger for Chip Cooling 10 This page intentionally left blank ...
Страница 18: ...Vertiv XDU Liquid to Air Heat Exchanger for Chip Cooling 14 This page intentionally left blank ...
Страница 38: ...Vertiv XDU Liquid to Air Heat Exchanger for Chip Cooling 34 ...
Страница 42: ...Vertiv XDU Liquid to Air Heat Exchanger for Chip Cooling 38 This page intentionally left blank ...
Страница 52: ...Vertiv XDU Liquid to Air Heat Exchanger for Chip Cooling 48 This page intentionally left blank ...
Страница 56: ...Vertiv XDU Liquid to Air Heat Exchanger for Chip Cooling 52 This page intentionally left blank ...
Страница 58: ...Vertiv XDU Liquid to Air Heat Exchanger for Chip Cooling 54 This page intentionally left blank ...
Страница 59: ...Appendix B Performance Curves Figure B 1 Liebert XDU Performance Test Results 45 C 113 F LFT 55 ...
Страница 62: ...Vertiv XDU Liquid to Air Heat Exchanger for Chip Cooling 58 This page intentionally left blank ...
Страница 64: ...Vertiv XDU Liquid to Air Heat Exchanger for Chip Cooling 60 This page intentionally left blank ...
Страница 74: ...Vertiv XDU Liquid to Air Heat Exchanger for Chip Cooling ...