Water Impurity or Condition
Corrective Method
Particles (dp < 0.3 mm)
Filter the water.
Excessive hardness
Soften the water by ion exchange.
Moderate level of particles and hardeners
Add dispersion or stabilization agents.
Moderate level of chemical impurities
Add deadening agents and inhibitors.
Biological impurities (bacteria and algae)
Add biocides.
Table 6.6 Water Impurity
Hydrological Data
Recommended Purity Levels
pH values
(7 - 10,5)
Carbonate hardness
(3 - 8) °dH
Free carbon dioxide
(8 - 15) mg/dm3
Combined carbon dioxide
8 - 15mg/dm
3
Aggressive carbon dioxide
0mg/dm
3
Sulfides
< 10mg/dm
3
Oxygen
< 50mg/dm
3
Chloride ions
< 250mg/dm
3
Sulphate ions
< 10mg/dm
3
Nitrates and nitrites
< 7mg/dm
3
COB
< 5mg/dm
3
Ammonia
< 5mg/dm
3
Iron
< 0.2mg/dm
3
Manganese
< 0.2mg/dm
3
Conductivity
< 30S/cm
Solid residue from evaporation
< 500mg/dm
3
Potassium manganese consumption
< 25mg/dm
3
Suspended matter
< 3mg/dm
3
Partial Flow Cleaning Recommended
3 -15 mg/dm
3
Full Flow Cleaning
> 15mg/dm
3
Table 6.7 Hydrological Data
6 Piping Requirements
27
Содержание Liebert XDU 060
Страница 1: ...Liebert XDU Liquid to Air Heat Exchanger for Chip Cooling Installer User Guide 600 mm Wide ...
Страница 10: ...Vertiv XDU Liquid to Air Heat Exchanger for Chip Cooling 6 This page intentionally left blank ...
Страница 14: ...Vertiv XDU Liquid to Air Heat Exchanger for Chip Cooling 10 This page intentionally left blank ...
Страница 18: ...Vertiv XDU Liquid to Air Heat Exchanger for Chip Cooling 14 This page intentionally left blank ...
Страница 38: ...Vertiv XDU Liquid to Air Heat Exchanger for Chip Cooling 34 ...
Страница 42: ...Vertiv XDU Liquid to Air Heat Exchanger for Chip Cooling 38 This page intentionally left blank ...
Страница 52: ...Vertiv XDU Liquid to Air Heat Exchanger for Chip Cooling 48 This page intentionally left blank ...
Страница 56: ...Vertiv XDU Liquid to Air Heat Exchanger for Chip Cooling 52 This page intentionally left blank ...
Страница 58: ...Vertiv XDU Liquid to Air Heat Exchanger for Chip Cooling 54 This page intentionally left blank ...
Страница 59: ...Appendix B Performance Curves Figure B 1 Liebert XDU Performance Test Results 45 C 113 F LFT 55 ...
Страница 62: ...Vertiv XDU Liquid to Air Heat Exchanger for Chip Cooling 58 This page intentionally left blank ...
Страница 64: ...Vertiv XDU Liquid to Air Heat Exchanger for Chip Cooling 60 This page intentionally left blank ...
Страница 74: ...Vertiv XDU Liquid to Air Heat Exchanger for Chip Cooling ...