BATTERY
User Manual 10H52246UM60 - Rev. 1 - 01/2017
55
3. Leave sufficient vertical clearance between the top of the batteries and the layer installed above them to enable
personnel to monitor and service them.
4. Install the batteries starting from the bottom layer and working up, so as to avoid situations where the center of
gravity is too high. Make sure that the batteries are installed correctly and that they are protected from vibration
and shocks.
6.7.2
Battery Connection
1. All the battery cabinets or battery racks must be connected together and grounded correctly.
2. When multiple batteries are used, they must be connected in series and then in parallel. Before loading and
power-up, check that the total voltage of the batteries is as specified. The negative and positive poles of the
batteries must be connected to the negative and positive battery terminals of the UPS according to the labels on
the battery and UPS. This is very important because connecting the battery poles to the wrong UPS battery
terminals can cause explosions and fire, and may result in damage to the battery and UPS, as well as injuries to
personnel.
3. Once the battery cable connections have been completed fit the insulating shields on the terminals.
4. When connecting the cable between battery terminal and protection device, connect the cable to the protection
device terminal first.
5. The bending radius of the cable must be greater than 10D, where D corresponds to the outer diameter of the
cable.
6. Once the battery cables have been connected, DO NOT pull on the battery cable or the cable terminal.
7. Do not cross the battery cables during the connection, and do not tie the battery cables together.
8. See Figure 6-1 for battery connection.
W14
W13
W03
W02
W12
W01
W11
BAT+
W04
W15
W10
BAT-N
W05
W16
W06
W17
W07
W18
W08
BAT-
Battery tray 1
PP terminal of W01 connects to PP terminal of W12
Battery tray 2
Battery tray 3
Battery tray 4
Battery tray 5
Battery tray 6
Battery tray 7
Battery tray 8
Figure 6-1
Connection for internal batteries (40-block)
6.8
Design Of Battery Room
Pay particular attention to the following items, irrespective of the type of installation (refer to Figure 6-2):
Layout of cells
W09
W09
W09
W09
W09
W09
W09
W09