OPTION
User Manual 10H52246UM60 - Rev. 1 - 01/2017
71
W21(+)
W20 (N
)
W19 (-
)
Hex sems screw M6*16
Torque value: 4.8N.m
Holes for cables binding
Holes for cables binding
Figure 8-6
Installing internal battery fuse and battery cables (front view)
3. Open the cabinet front door, remove the screws in order to open the battery compartment door (see Figure 8-7),
and keep them.
Battery compartment door
Figure 8-7
Opening the battery compartment door
Warning
The following operations on the battery and battery tray may only be operated by authorized service engineers wearing the
appropriate insulating safety gloves.
4. Place the batteries into corresponding positions on battery trays, one by one, in accordance with the internal
battery connection layout, as shown in Figure 6-1, and then use M6*20 SEMS screws/spring washers/flat washers