OPERATOR CONTROL AND DISPLAY PANEL
40
User Manual 10H52246UM60 - Rev. 1 - 01/2017
Table 4-7
D
escription of menu window and data window items
Menu
Item
Explanation
Mains
L-N voltage (V)
Phase voltage
L-N current (A)
Phase current
Frequency (Hz)
Input frequency
L-L voltage (V)
Line voltage
Power factor
Power factor
Bypass
L-N voltage (V)
Phase voltage
Frequency (Hz)
Bypass frequency
L-L voltage (V)
Line voltage
OutPut
L-N voltage (V)
Phase voltage
L-N current (A)
Phase current
Frequency (Hz)
Output frequency
L-L voltage (V)
Line voltage
Power factor
Power factor
Load
S
out
(kVA)
S
out
: apparent power
P
out
(kW)
P
out
: active power
Q
out
(kVAR)
Q
out
: reactive power
Load level (%)
Load (expressed as a percentage of the UPS nominal load)
Crest factor
Output current crest factor
System
S
out
(kVA)
S
out
: apparent power
P
out
(kW)
P
out
: active power
Q
out
(kVAR)
Q
out
: reactive power
Single unit, no parallel
system data
Displayed in this data window when the UPS is configured as a single unit
Battery
Battery voltage (V)
Battery bus voltage
Battery current (A)
Battery bus current
Battery temperature
(°C)
Built-in battery temperature
Battery remain time
(Min.)
Remaining battery backup time
Battery capacity (%)
Percentage of battery life when compared to a new battery
Battery boost charging
Battery is boost charging
Battery float charging
Battery is float charging
Battery is not
connected
Battery is not connected
Event
(active alarm)
Display the active alarms
Records
(alarm history)
Display the alarm history
Language
(language option)
Permits the user to select from 17 available LCD display languages
Settings
Display contrast
Adjust the LCD contrast
Date format set
Three formats selectable: MM/DD/YYYY, DD/MM/YYYY, YYYY/MM/DD
Date & time
Set the date and time
Comm1 baud rate
Set the Intellislot port 1 communication baud rate
Comm2 baud rate
Set the Intellislot port 2 communication baud rate
Comm3 baud rate
Set the Intellislot port 3 communication baud rate
Communication address
Applicable to RS485 communication
Single Group Batt Cap
Set the capacity of battery unit
Battery Cells Number
Set the battery cells connected to the UPS
Equalize Charge
Allowed
Battery boost charge is enabled or disabled
Temp Compensation
Enabled, Disabled
Shared Battery
Enabled, Disabled
System Configuration
Single, Parallel
Parallel Requisite units
Basic number of single modules in parallel system
Parallel Redundant
units
Redundant number of single modules in parallel system
Parallel ID
Provide an ID code for a single module in a parallel system, when 'Parallel' is
set
ECO Mode
Normal, ECO
Output Frequency Level
Set the system output frequency (unit: Hz); 50/60
Output Voltage Level
The voltage between phase line and phase line
LBS Function
NONE, SLAVE, MASTER
Command password
The user can modify the command password
Protocol Velocity
Command
(initiate, stop
Battery maintenance
test
20% battery capacity is used for battery maintenance test. Load must be
between 20% and 80%