BTRM Battery Test Remote Monitoring System – User Guide V3.2 |
ã
2021 Ventev | LIT SKU: 09834
22
10.1.1
DNP Addressing
Master and Device addressing supports values between 0 and 65535.
Confirm with your selected protocol what address values are allowable.
10.1.2
DNP Retry Settings
Retry settings for unsolicited messages range between 0 (no retries) and 254 with
setting of 255 causing continuous retries.
Elapsed time between retries 0 to 255 seconds (settings below 5 seconds not
recommended).
10.1.3
DNP3 Communications Interface
TCP/IP
Configurable: TCP/IP Port (Default 20000)
Configurable: TCP/IP Unsolicited message destination IP address
10.1.4
MODBUS RTU and DNP3 over RS232
BTRM supports RS232 3 wire RS232 using standard connections pin 2, 3, and 5 on
DB9 connector.
Baud Rates
Selectable at: 1200, 2400, 4800, 9600, 19200, 38400, 57600, 115200
Data Format: Data 8 bits, Stop Bits 1,
Parity Selection
Modbus
Typical Parity: Even
DNP3
Typical Parity: None